TO THE OWNER
Congratulations on your purchase of one of our highly versatile Cima projection screens representing
“Top of the Class” in standard commercial and residential projection screens Please take a moment to
review this manual as it will help ensure you many years of trouble-free service from your new Cima by
Stewart Filmscreen product
ABOUT YOUR CIMA AC NT ELECTRISCREEN
The Cima Above Ceiling Non-Tensioned ElectriScreen is designed for ease of installation The Cima
Above Ceiling Non-Tensioned features a self-finishing face-plate There are no user-servicable parts
contained within the unit
IMPORTANT SAFETY INFORMATION
SAFETY PRECAUTIONS
`
`
Carefully read the instructions appropriate for your needs
`
`
This screen must be installed by a qualified electrician
`
`
For supply connections, use wires rated for at least 75 C
`
`
Use copper or aluminum conductors
`
`
For indoor use only
`
`
Do not connect low-voltage to line-voltage power
`
`
Article 725-54(a), (1) Exception No 3 (NEC) or Canadian CE Code Handbook, Rule 16-212, Sub Rule (4)
requires segregation between line-voltage and Class 2 (low-voltage) circuits Low-voltage / network
wires should enter enclosure boxes through separated openings Also, conductors shall be separated
by at least 1/4” or segregated by barriers Check with your local electrical inspector for compliance
with local / national codes and wiring practices
`
`
Earth ground terminal connection must be made as shown in wiring diagrams
`
`
Proper short-circuit and overload protection must be provided at the circuit breaker distribution
panel You can use up to a 20A maximum circuit breaker with adequate short-circuit breaking
capacity for your installation