Stephill DSE 6110 MK3 User & Fault Finding Manual Download Page 4

Stephill Generators SSDP30-70 -  DSE 6110 Module User Guide

Issue 2

Stop/Reset Mode

Manual Mode

Start

Menu Navigation

Used for navigating the instrumentation and configuration screens.

Example

Status

Engine

Generator

(page)

(page)

   (page)

…And so on until the desired page is reached.

Auto Mode

Alarm Mute / Lamp Test

This button silences the audible alarm in the controller and illuminates all of the LED's 
on the module's facia as a lamp test function.

Pressing the 

Start

 button in 

Manual Mode

 will begin the generator starting process 

and run the generator in 

Manual Mode

.

If an alarm becomes active while viewing the status page, the display shows the 

Alarms 

page to draw the operators attention to the alarm.

This button places the module into it's 

Auto Mode

. This mode allows the module to 

control the function of the generator automatically. The module monitors the 

Remote 

Start Input

 and once a start request is made, the set is automatically started. Upon 

removal of the start signal the generator will stop.

It is possible to scroll to display the different pages of information 
by repeatedly operating the 

Next

 and 

Previous

 page buttons.

Once selected, the page remains on the LCD display until the user selects a different 
page, or after an extended period of inactivity (LCD Page Timer), the module reverts to 
the status display.

If no buttons are pressed upon entering an instrumentation page, the instruments 
displayed are automatically subject to the setting of the 

LCD Scroll Timer

.

Alternatively, to scroll manually through all instruments on the 
currently selected page, press the 

Instrumentation Scroll 

buttons.

This button places the module into its 

Manual Mode

. Once in 

Manual Mode

 the 

module will then respond to the 

Start 

button to start the generator and run it off load.

Icon

Description

This button places the module into its Stop/Reset Mode. This clears any alarm 
conditions for which have triggered and criteria have been removed. If the engine is 
running and the module is put into Stop mode, the fuel supply de-energises and the 
engine comes to a standstill. 

Button Description

JD/08/18

4

Summary of Contents for DSE 6110 MK3

Page 1: ...Issue 3 June 2020 SSDP30 70 Range DSE 6110 MK3 Control Module User Fault Finding Guide...

Page 2: ...e Load Applied is Balanced and the Total Load How to Check the Generator Frequency How to Check the Engine Instruments Engine Speed Engine Oil Pressure Engine Coolant Temperature Engine Battery Voltag...

Page 3: ...f the DSE6110 MK3 module as configured on Stephill Generators and to gain access to the information available It has been produced as a How to guide Once the 12V supply has been connected to the modul...

Page 4: ...on removal of the start signal the generator will stop It is possible to scroll to display the different pages of information by repeatedly operating the Next and Previous page buttons Once selected t...

Page 5: ...is displayed on the screen Fig 2 then this indicates that the generator cannot be started due to an active Shutdown on the module Once you have issued a start request and the generator has started and...

Page 6: ...ven balanced as possible will eliminate nuisance Over Current or Over Under Voltage shutdown alarms If the page automatically scrolls to another press either of the Instrument Scroll buttons until you...

Page 7: ...buttons until across the top of the screen it reads Generator Then press one of the Instrument Scroll buttons until Generator Load is displayed at the top of the screen Fig 9 Standby kW Is the maximum...

Page 8: ...nerator Frequency is displayed at the top of the screen page Fig 11 The typical no load frequency should be between 52 0 and 53 0 Hz If at no load the frequency is as low as 51 5 Hz then it would be a...

Page 9: ...running or at standstill you will see one of two screens showing the current fuel level Fig 18 Fig 19 shows no registered fuel level this is the fuel level screen when the generator is at standstill n...

Page 10: ...Instrument Scroll buttons until Service Hours is displayed at the top of the screen page Fig 21 The Service Hours Alarm screen is a count down timer when the timer reaches zero hours a Warning Alarm...

Page 11: ...t to change with module updates To view the Event Log use the Next or Previous buttons until at the top of the screen it reads Event Log Fig 23 press one of either the Instrument Scroll buttons to vie...

Page 12: ...hutdown Common Fault Conditions Emergency Stop shutdown Low Oil Pressure shutdown Oil Pressure Sender Sender Fault shutdown Fail To Stop High Engine Temperature shutdown Coolant Level shutdown Charge...

Page 13: ...module STEPHILL GENERATORS LTD STRESS THAT THE ULTIMATE RESPONSIBILTY FOR THE SAFE USE OF THE GENERATOR RESTS WITH THE USER Recommended Checks Before Attempting Any Fault Finding Before starting the g...

Page 14: ...reen on the DSE 6110 module user guide page 4 Start the generator and check that all the voltages displayed are correct If there is an large imbalance of voltages then check the following The module d...

Page 15: ...rap filter It maybe also worth checking the air filter s are in good condition replace is necessary If the above fails to raise or rectify the issue it may be worth checking the engine for possible ma...

Page 16: ...rest Emergency Stop Shutdown Common Fault Conditions Below is a general guide for the most common fault conditions on a Stephill Generator using a DSE 6110 Mk3 control module Checks Tests Check wirin...

Page 17: ...agnetic connection behind the hardwire door and control box Check wiring from the switch to the DSE 6110 wire No 46 Check switch operation Open from ground to fault Check all MCCB MCB s are in the ON...

Page 18: ...k Fuel pump operational press and hold the prime button if applicable 12V present between wires 51 1 on the fuel pump plug when the prime button is pressed Replace 12V fuel lift pump Yes Disconnect th...

Reviews: