How to Check the Control Module "Event Log"

Example

Fig.23

IDMT Alarm

If the 

IDMT Alarm

 

is enabled, the controller begins following the IDMT ‘curve’ when the 

trip 

level is passed.

If the 

trip 

is surpassed for an excess amount of time (set at 1 hour) the 

IDMT Alarm

 

triggers a shutdown.

High Current Shutdown

 is a latching alarm and stops the generator.

Remove the load then press the             button to reset the module.

The higher the overload the faster the trip. The speed of the trip is dependent upon the fixed formula.

T = t / ((IA / IT) – 1) 2

Where: 

is the tripping time in seconds.

IA

 is the actual current of the most highly loaded line (L1 or L2 or L3).

IT

 is the delayed over-current trip point.

Over 110% load would issue an immediate shutdown on the generator.

The module maintains a log of past alarms and selected status changes. Currently the module is capable of 
storing the last 250 log events. This is always subject to change with module updates.

To view the 

Event Log

, use the 

Next

 or 

Previous

 buttons until at the top of the screen it reads 

Event Log 

Fig.23, press one of either the

 Instrument Scroll

 buttons to view the next or last event. The 

Event Log 

always 

contains the most recent events, along with the engine hours.

With typical settings, this allows for overload of the set to the limits of the 

Typical Brushless Alternator  

whereby up to 110% overload is permitted for 1 hour.

t

 is the time multiplier setting and also represents the tripping time in seconds at twice full load (when IA / IT 

= 2).

This setting is to provide normal running of the generator up to 100% full load. If full load is surpassed, the 

Immediate Warning 

alarm is triggered, the set continues to run.

The effect of an overload on the generator is that the alternator windings begin to overheat; the aim of the 

IDMT Alarm

 

is to prevent the windings being overload (heated) too much. The amount of time that the set 

can be safely overloaded is governed by how high the overload condition is.

This is event 1

Engine hours

Coolant Temp High 

Shutdown 

Event Log 

196h    21m 

Next and Previous 

Instrument Scroll 

JD/08/18

11

Summary of Contents for DSE 6110 MK3

Page 1: ...Issue 3 June 2020 SSDP30 70 Range DSE 6110 MK3 Control Module User Fault Finding Guide...

Page 2: ...e Load Applied is Balanced and the Total Load How to Check the Generator Frequency How to Check the Engine Instruments Engine Speed Engine Oil Pressure Engine Coolant Temperature Engine Battery Voltag...

Page 3: ...f the DSE6110 MK3 module as configured on Stephill Generators and to gain access to the information available It has been produced as a How to guide Once the 12V supply has been connected to the modul...

Page 4: ...on removal of the start signal the generator will stop It is possible to scroll to display the different pages of information by repeatedly operating the Next and Previous page buttons Once selected t...

Page 5: ...is displayed on the screen Fig 2 then this indicates that the generator cannot be started due to an active Shutdown on the module Once you have issued a start request and the generator has started and...

Page 6: ...ven balanced as possible will eliminate nuisance Over Current or Over Under Voltage shutdown alarms If the page automatically scrolls to another press either of the Instrument Scroll buttons until you...

Page 7: ...buttons until across the top of the screen it reads Generator Then press one of the Instrument Scroll buttons until Generator Load is displayed at the top of the screen Fig 9 Standby kW Is the maximum...

Page 8: ...nerator Frequency is displayed at the top of the screen page Fig 11 The typical no load frequency should be between 52 0 and 53 0 Hz If at no load the frequency is as low as 51 5 Hz then it would be a...

Page 9: ...running or at standstill you will see one of two screens showing the current fuel level Fig 18 Fig 19 shows no registered fuel level this is the fuel level screen when the generator is at standstill n...

Page 10: ...Instrument Scroll buttons until Service Hours is displayed at the top of the screen page Fig 21 The Service Hours Alarm screen is a count down timer when the timer reaches zero hours a Warning Alarm...

Page 11: ...t to change with module updates To view the Event Log use the Next or Previous buttons until at the top of the screen it reads Event Log Fig 23 press one of either the Instrument Scroll buttons to vie...

Page 12: ...hutdown Common Fault Conditions Emergency Stop shutdown Low Oil Pressure shutdown Oil Pressure Sender Sender Fault shutdown Fail To Stop High Engine Temperature shutdown Coolant Level shutdown Charge...

Page 13: ...module STEPHILL GENERATORS LTD STRESS THAT THE ULTIMATE RESPONSIBILTY FOR THE SAFE USE OF THE GENERATOR RESTS WITH THE USER Recommended Checks Before Attempting Any Fault Finding Before starting the g...

Page 14: ...reen on the DSE 6110 module user guide page 4 Start the generator and check that all the voltages displayed are correct If there is an large imbalance of voltages then check the following The module d...

Page 15: ...rap filter It maybe also worth checking the air filter s are in good condition replace is necessary If the above fails to raise or rectify the issue it may be worth checking the engine for possible ma...

Page 16: ...rest Emergency Stop Shutdown Common Fault Conditions Below is a general guide for the most common fault conditions on a Stephill Generator using a DSE 6110 Mk3 control module Checks Tests Check wirin...

Page 17: ...agnetic connection behind the hardwire door and control box Check wiring from the switch to the DSE 6110 wire No 46 Check switch operation Open from ground to fault Check all MCCB MCB s are in the ON...

Page 18: ...k Fuel pump operational press and hold the prime button if applicable 12V present between wires 51 1 on the fuel pump plug when the prime button is pressed Replace 12V fuel lift pump Yes Disconnect th...

Reviews: