- 22 -
- 23 -
Dimensions
(L × D × H in mm)
True Presence UP: 103 × 103 × 50
True Presence AP: 123 × 123 × 45
Hallway UP:
103 × 103 × 66.5
Hallway AP:
123 × 123 × 62
Input voltage
220-240 V, 50 / 60 Hz
Power consumption
• Stand-by
True Presence:
< 1 W
Hallway:
< 0.5 W
Capacity,
switching output 1:
(COM
1/COM
2)
Incandescent/halogen lamp load
2,000
W
Fluorescent lamps, electronic ballast
1,500
W
Fluorescent lamps, uncorrected
1,000
VA
Fluorescent lamps, series-corrected
400
VA
Fluorescent lamps, parallel-corrected
1,000
VA
Low-voltage halogen lamps
2,000
VA
LED
<
2 W
100
W
2
W
<
LED
<
8
W
300
W
LED
>
8
W
600
W
Capacitive load
176
μF
Capacity,
switching output 2:
(COM
2 only)
max. 230 W/230
V
max. 1 A (cos φ = 1) for HVAC
(heating/ventilation/air-conditioning)
Time setting
COM1 relay
Hallway: 10 s - 60 min / IQ mode
True Presence: 30 s - 60 min / IQ mode
COM2 relay
Stay-ON time: 1 min - 120 min
Switch-ON delay: 0 min - 10 min
Twilight setting
2-2,000
l
ux
Reach
True Presence:
Ø 9 m True Presence (mounted up to a height of
max. 4 m)
Ø 15 m presence
Ø 15 m movement
(can be set to within one centimetre)
Hallway: 25 × 3 m x 2.8 m
Angle of coverage
360°
Mounting height
True Presence:
2.8-12 m
Hallway:
2-4 m
Optimum mounting height: 2.8 m
IP rating
IP54 (surface-mounted version only)
Temperature range
-20°C to +50°C
True Presence frequency
7.2 GHz (responds to micro-movements resulting
from the vital functions)
11. Technical specifications
GB