WARRANTY
Dimensions (Ø × D)
Ø 80 × 20.5 mm
Power consumption
4 mA / 2-DALI users,
12-22.5 V
, no SELV
Sensor technology
Passive infrared (IR)
DALI interface
DALI control line (multi-master capability
for communication with the DALI Application
Controller/DALI sensor), DALI start-up time < 1 s
Detection zone
360° for a 90° angle of aperture
(84 detection beams and 168 detection zones)
Light measurement
2-1000 Lux
Reach
4 × 4 m presence, radial,
6 × 6 m tangential / 2.8 m height
IP rating
IP20
Temperature range
0°C to + 40°C
10. Technical specifications
Malfunction
Cause
Remedy
No power at the sensor
■
Fuse has tripped, not
switched ON, break in
DALI wiring
■
Short circuit
■
Activate, change fuse,
turn ON mains switch,
check DALI wiring with
voltage tester
■
Check connections
Light level not being
communicated
■
Break in wiring
■
DALI power supply
faulty
■
Check cable
Sensor sending motion
detection signal when it
should not
■
There is interference,
e.g. fan, airconditioning
system or other source
of heat, in the detection
zone
■
Animals moving in
detection zone
■
Wind is moving
paper or plants in the
detection zone
■
Sunlight is shining on
the lens
■
Sudden temperature
change due to air
expelled from fans,
open windows, air-
conditioning systems
or other sources of
heat
■
Sensor near Wi-Fi
or other wireless
communication source
■
Adjust detection zone
or fit shrouds, increase
distance
■
Adjust zone or fit
shrouds
■
Change detection zone
■
Mount sensor in a
protected place or
change zone
■
Adjust detection zone
or install in a different
place
■
Install at least 2 m
away from the wireless
communication source
Sensor reach change
■
Differing ambient
temperatures
■
Use shrouds to
define detection zone
precisely
11. Troubleshooting