- 15 -
- 14 -
GB
1. About this document
Please read carefully and keep in a safe place.
– Under copyright. Reproduction either in whole or in part only with our
consent.
– Subject to change in the interest of technical progress.
Symbols
!
Hazard warning!
...
Reference to other information in the document.
2. General safety precautions
• Disconnect the power supply before performing any work on the unit.
• During installation, the electric power cable to be connected must not be
live. Therefore, switch off the power first and use a voltage tester to make
sure the wiring is off-circuit.
• Installing the sensor involves work on the mains power supply. This work
must therefore be carried out professionally in accordance with national
wiring regulations and electrical operating conditions. (e.g.
DE:
VDE 0100,
AT:
ÖVE / ÖNORM E8001-1,
CH:
SEV 1000)
• Only use genuine replacement parts.
• Repairs may only be made by specialist workshops.
3. IR Micro
Proper use
– Presence detector suitable for indoor ceiling mounting.
The sensor is connected to the control unit via a DALI bus.
The sensor uses the DALI line for communication and for supplying power.
Package contents
(Fig. 1)
Product dimensions
(Fig. 2)
Product components
(Fig. 3)
A
Fitting frame
B
Plug connection
C
Sensor enclosure with lens
D
Designer trim
4. Installation / wiring
• Switch OFF power supply.
(Fig. 4)
A clip-on ceiling adapter or a frame for fitting onto a mounting box is provided
(Fig. 5)
.
– Wiring diagram
(Fig. 6)
Wiring up the sensor switch: under section 6 of VDE 0100520, a multi-core lead
containing both the mains voltage leads as well as the control leads (e.g. NYM
5 × 1.5 mm²) may be used for the wiring between sensor and DALI Application
Controller.
The lead between DALI Application Controller and sensor must be no longer
than 300 m (with 1.5 mm²). After installing and switching ON, the sensor flashes
for 10 seconds.
Connecting the mains power supply lead
(Fig. 6)
Note on parallel connection:
Several sensors can be connected in a DALI-2 system. In this case,
the maximum number of DALI users must not be exceeded
(
➜
"10. Technical specifications"
)