I N S T A L L A T I O N
Installation – step 2
Water supply installation
Water supply specification & quality:
Water supply pressure: 15 to 80PSI [1 to 5bar]
Water supply temperature: 37 to 105°F [3 to 40°C]
RES electric steam humidifier can accept a wide range of water quality.
Untreated water will lead to scale deposits that will need to be regularly removed from steam chamber.
Use of additives such as scale inhibitor or corrosion inhibitors, disinfectants or other can impair the
normal operation of the humidifier and are not allowed.
Water supply conductivity: 1 to 1500
µ
S/cm
Water supply hardness: 0 to 16grains/gallon [0 to 15°gH][268mg CaCO
3
/l]
Water supply PH: 6.5 to 7.5
Water supply chloride content: 0 to 50ppm
Water supply
Flexible braided hose
(supplied)
Filter 10µm recommended
(by others)
Shut-off valve
(by others)
Figure 7 – water supply connection
Water supply connection:
1. Install a manual; shut off valve on the water main line.
2. If
steamOres
humidifier is supplied with tap water it is recommended to install a 10
µ
sediment
filter on the line. This filter will protect internal water fill valve from clogging.
3. A flexible braided hose is supplied for an easy and secure connection to the water supply inlet.
This hose is equipped with 12mm female swivel connection at one end and G3/4 on
steamOres
connection side.
13