I N S T A L L A T I O N
Installation – step 1
Positioning & Mounting
General guidelines for positioning
RES
electric steam humidifier should be positioned so that:
Length of the steam line (or hose) is as short as possible,
In case steam hose is used, the bend radius of 12in [300mm] is ensured
Humidifier is easily accessible for service
CAUTION. Risk of malfunction due to vibration. Do Not mount RES
electric steam
humidifier directly on ventilation duct
.
CAUTION. Risk of flooding.
Ensure that the local where steamOres steam humidifier
will be installed is equipped
with floor drain.
In case of no floor drain is available; installation of a water leak detector is required in order to prevent
any flooding in case of abnormal operation or service.
steamOres
steam humidifier should be installed in a well-ventilated and dry environment.
If local is subject to below freezing point temperature, activation of ant freezing function of the
steamOres
steam humidifier is required.
For outdoor installation please contact your steamOvap representative to order and install special
outdoor optional enclosure for RES.
steamOres
maximum ambient conditions:
Temperature: 41 to 113°F [+5 to +45°C]
Relative Humidity: 90%RH max (non condensing)
Ingress Protection for
steamOres
standard enclosure: IP30
10