07/07
Pub. No. 323-H
3. Steam Generator Electrical Installation
4. Optional Auto Drain Valve Connection
a)
b)
c)
d)
e)
Remove the six screws holding the electrical access
cover and remove cover.
Locate the supply line knockout. Mount proper
strain relief into knockout hole.
Strip back power cable’s outer insulation jacket
eight inches and insert into steam generator. Strip
back insulation ½” from the three (3) incoming
wires (two power and one ground).
Insert ground wire into grounding lug located on the
right side of the electrical compartment and secure.
CAUTION:
Be sure the ground wire does not come
in contact with a live electrical part.
Locate the terminal block in the upper portion of the
electrical box. Insert power wires into the power
lugs on the right of the terminal block and secure.
Open knockout for Auto Drain Valve conduit
connection.
Route flexible conduit from valve to knockout and
secure.
Connect two wires from valve to the two place
terminal strip provided (See figure 2).
a)
b)
c)
WARNING:
All power to the steam generator must
be turned off.
NOTE:
The plug and receptacle require a rating of
no less than 250V and proper amperage. Refer to
chart on page 4 for amperage rating.
After the walls are complete, the Steam Generator
and Control can be wired.
2. Electrical Rough-In
Route appropriate power cable to the location the
Steam Generator will be installed. If receptacle is
desired, mount the box for the receptacle near the
location of the Steam Generator (See Figure 3:
Typical Installation).
a)
Electrical Installation Instructions
Models:
SM-12 and SM-15
IMPORTANT:
the warranty of this product is voided if it is used in a commercial application or for anything other than a
residential steambath installation. All electrical connections must be performed by a licensed electrician in accordance
with Local and National Electric Codes.
Steambath Generators
C
US
®
LISTED 995C
The Steamist “SM” generator operates with one or two
controls appropriately located inside and/or outside the
steamroom. It’s small enough in size to be tucked away
using very little space in a vanity, closet, basement, or an
insulated attic, but large enough to provide steam for most
residential baths.
The Steamist “SM” Steambath Generator comes
factory-assembled carefully wired and tested.
Proper electrical supply (208 or 240 Volt): See rating
label on Steam Generator and Chart on back page.
Determine proper size of wire, voltage, amperage,
and phase for the Steam Generator. Only UL rated
90°C wire can be used.
In-line fuse/circuit breaker required: Fuse/circuit
breaker to be installed must be sized in accordance
with chart on back page. Do NOT install a GFI
(Ground Fault Interrupter) to this equipment (per
article 210-8 in the National Electric Code).
Route power supply cable to the location where the
Steam Generator will be installed (before walls are
closed).
1. Pre-Installation
a)
b)
c)
NOTE:
The TC-110, TC-135, DSC-425, and DSP
Controls are designed to work with all Steamist “SM”
Generators.
Optional Auto
Drain Installed
Water Inlet
⅜“ Compression
Fitting
¾“Safety
Relief Valve
¾“ Steam
Outlet
Electrical
Panel Cover
Knock-outs for
Electrical Supply Line
Knock-out for
Control Cable
- 1 -
WARNING:
Elderly persons, pregnant women, or those suffering from heart disease, high blood
pressure, diabetes, or who are otherwise not in good health, do not use this device unless
directed to do so by a physician. Also, do not use steambath while under the influence of alcohol.
!
Figure 1
Steam Generator
Install Upright and Level