STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10B Pellistor Gas Detector
TD18/008
Issue:
10
Change Note:
1904
Page 42
Compliance with the Essential Health and Safety Requirements has been
assured by compliance with:
EN 60079-0: 2018 EN 60079-1 : 2014
Electrical data
Power supply - 8Vdc to 24Vdc, 5W
Installation instructions
The cable entry devices and blanking elements of unused apertures shall be
of a certified flameproof type, suitable for the conditions of use and correctly
installed.
With the use of conduit, a suitable certified sealing device such as a stopping
box with compound shall be provided immediately at the entrance to the
flameproof enclosure.
A copy of the certificate is available for download from:-
www.status-scientific.com