STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10B Pellistor Gas Detector
TD18/008
Issue:
10
Change Note:
1904
Page 23
4.6.1.
E : 1
– Sensor Zero
Refer to section 5.1.1. for sensor calibration details.
4.6.2.
E : 2
– Sensor Span
Refer to section 5.1.2. for sensor calibration details.
4.6.3.
E : 3
– Sensor Fsd
This Feature sets the FSD of the instrument. It must be matched to the
sensor.
•
Press MENU to open the menu system.
•
Using the
or
buttons, select menu option:
E:3
•
Press
.
•
Using the
or
buttons, change the display to the required
setting.
•
Press
to store the new value.
Note: Pressing the MENU button rather than the
button
exits without any change.
•
Press MENU to close the menu system.
4.6.4.
E : 4
– Output Zero (4mA)
Refer to section 5.2.1. for output calibration details.
4.6.5.
E : 5
– Output Span (20mA)
Refer to section 5.2.2. for output calibration details.