SYMPTOM
POSSIBLE CAUSE
ACTION
DISPLAY IS BLANK
No power
Check power supply connections
DISPLAY SHOWS
Input is out of range
Check that the engineering high value
(above maximum)
is correct
DISPLAY SHOWS
Input is out of range
Check that the engineering low value
(below minimum)
is correct
‘
DP Err
’ IS DISPLAYED
The displayed value (excluding total)
This can occur if the PV is configured
is greater than 6 digits (i.e. 999999)
outside of the displayable range
‘
OP CAL
’ IS DISPLAYED
The output pod has been corrupted
Re-configure output. If the error is still
present replace the output pod
‘
IP CAL
’ IS DISPLAYED
The input calibrated data has been
Re-input calibration data. If the error is
corrupted still present replace the unit
TOTAL DISPLAY AFTER
Total has increased above the
Press all three front panel keys together
READING HIGH NOW
displayed 6 low digits of the total
and check the 6 high total digits
SHOWS A LOW VALUE
15.0 FAULT FINDING