background image

Page 3

The power supply rating will be indicated on the top of the instrument, 

ENSURE IT IS CORRECT FOR THE 

APPLICATION.

THE MAINS SUPPLY TO THE EQUIPMENT MUST BE PROTECTED BY AN EXTERNAL 1 A FUSE AND A SUITABLE
SWITCH OR CIRCUIT BREAKER WHICH SHOULD BE NEAR THE EQUIPMENT.

NOTE: USE 600 VRMS CABLE (0.5 TO 1.5) mm

²

.

Wires are retained by screws.  Ensure that the exposed section of the wire is fully inserted and that no
loose strands are exposed.

All sensor connections are made via the five way "fast wiring" socket at the rear of the unit (wire size (0.5
to 1.5) mm²).

NOTE: THERMOCOUPLE, RTD AND VOLTAGE INPUT SCREENED CABLE IS RECOMMENDED FOR RUNS
GREATER THAN 10 m.

To make a connection: Insert small screwdriver blade into tension clamp orifice 

(1),

push and twist to

deflect clamp into open position. Do not lever screwdriver thus forcing connector body sideways. Insert
conductor tail sufficiently into 

(2)

then release screwdriver.  Ensure no loose wire strands protrude.

Page 4

Power must be removed from unit before adding/removing a pod. Slot 1 (alarm 1A and 1B) should be 
positioned on the left side of the unit looking from the front to correspond to front panel alarm indicator,
Slot 2 (alarm 2A and 2B) is positioned on the right.

To install an Option Pod, slide back the cover to its next engaging position and push the pod connection
within the mating connector. To remove an option pod, disengage the supporting latch situated beneath
the pod by pushing the back cover forward, the pod can then be lifted away from the instrument connector.

The relay pod has two "change over" relays with a common wiper.

NOTE: USE 600 VRMS CABLE (0.5 TO 1.5) mm²

NOTE: ANY CIRCUIT WITH AN AC POTENTIAL GREATER THAN 33 V RMS AND 46.7 V PEAK MUST BE 
PROTECTED WITH A 5 A(T) FUSE WHEN CONNECTED TO THIS POD.

3.3 POWER SUPPLY

3.4 SENSOR CONNECTIONS

4.0 OPTION PODS

(+) L N (-)

1
2

1

2

3

4

5

NO

NC

WIPE

R

NO

NC

4.1 INSTALLING PODS

4.2 DUAL RELAY POD. POD-3000/02

Summary of Contents for DM3600A

Page 1: ...EVICE 13 12 0 INPUT MENU STRUCTURE 14 17 13 0 OUTPUT MENU STRUCTURE 18 20 14 0 SYSTEM MENU STRUCTURE 21 22 15 0 FAULT FINDING 23 Status Instruments Ltd Status Business Park Tewkesbury Glos GL20 8FD Tel 44 0 1684 296818 Fax 44 0 1684 293746 Email sales status co uk Web www status co uk 52 314 2358 02 Issue Web 4 DM3600A INDEX Single Channel Universal Input 6 Digit Indicator with Flow Totalizer Func...

Page 2: ...on to an Installation over voltage Category II supply pollution degree 2 The supply voltage and frequency must remain within the limits stated on the product label The mains supply to the unit must be protected by an external 1 A fuse and a suitable switch or circuit breaker must be located close to the equipment in order to isolate the supply SIGNAL INPUT OUTPUTS All signal input and communicatio...

Page 3: ...ert conductor tail sufficiently into 2 then release screwdriver Ensure no loose wire strands protrude Page 4 Power must be removed from unit before adding removing a pod Slot 1 alarm 1A and 1B should be positioned on the left side of the unit looking from the front to correspond to front panel alarm indicator Slot 2 alarm 2A and 2B is positioned on the right To install an Option Pod slide back the...

Page 4: ...ease contact your supplier When fitted this option provides the user with either 4 or 2 wire RS485 serial communications together two digital inputs Connections are made via a RJ45 connector A 0 5 m interface is supplied with this Page 5 Page 6 Material ABS PC Flammability IEC707 FV0 UL 94VO Weight 230 g Panel cut out 92 x 45 mm 1 2 3 4 5 R Load 1 2 3 4 5 V R Load Max RLoad 1 K 4 3 ISOLATED 4 TO 2...

Page 5: ...stom 999 to 9999 Accuracy Linearisation Cold Junction Error Cold Junction Tracking Cold Junction Range 0 04 FS 0 04 reading or 0 5 C whichever is greater BS 4937 IEC 584 3 Custom 1 0 5 C 0 05 C C 20 to 60 C Thermal Drift Zero 4u V C Span 0 02 C Voltage Input Basic Accuracy 0 04 FS 0 04 of reading Thermal Drift 0 01 C Input Impedance 1 MΩ Linearity Linear X X3 2 X5 2 Custom Range 100m V 1 V 5 V 10 ...

Page 6: ...BUS RTU protocol and can be configured using Status own M Config software Physical Layer 4 wire or 2 wire half duplex RS485 Protocol MODBUS RTU format Breakdown Isolation 500 VAC Maximum Fan out 32 units can be increased with repeaters Termination Standard RS485 The DM3600 is configured using the three keys on the front panel The unit has two modes of operation The first is Run mode This will auto...

Page 7: ... If enabled this gives access to the relevant alarm setpoints To revert to Run mode press these keys up to 4 times Show electrical value e g 4 to 20 mA input Shows secondary value i e total or rate If enabled this will clear total and or latched alarms Perform clear function Show upper 6 digits of Total RUN MODE RATE OR TOTAL DISPLAYED Edit setpoints menu shortcut Followed by Enter menu mode 8 2 R...

Page 8: ...1 100 mV Displayed if voltage input is selected Displayed if current input is selected nOnE None linear S9rOOt Square root rOOt32 Power 3 2 rOOt52 Power 5 2 USEr User defined Ni 1 20 Ni120 CA K Current Voltage JISC Pt100 USA Japanese USEr User defined RTD J J t T r R S S E E F F n N b B USEr User defined Thermocouple Pt100 Pt100 European SE9ntS Segments EntEr Enter Enter value In1 OUt1 Enter value...

Page 9: ...s simply required to choose the tyPE and Lin linearity type For CurEnt or uOLt input types the user can choose STndrd or AUtO scaling from the ScALE sub menu 12 1 INPUT MENU BLOCKS SE9ntS In1 OUt1 In2 OUt2 ENGINEERING LOW HIGH If Stndrd scaling is chosen the user will encounter En9LO and En9HI entries in order to manually scale the input to the relevant input_lo and input_hi values see table overl...

Page 10: ...factor and time base are used to scale the amount by which the total is incremented every second The total added every second is rate x factor time base x divider where time base is 160 or 3600 s The total displayed has a minimum number of 12 digits In normal running mode the 6 lower digits are shown by pressing the three front keys together the next 6 digits are shown RELAY OUTPUT MENU OUt 1 Outp...

Page 11: ...required when the flow exceeds 10 000 kg h the setpoint will be set to 10 000 ALARM ACTION This defines the behaviour of the alarm when the setpoint is reached HYSTERISIS The hysterisis value is the difference between the points at which the alarm triggers and releases expressed in the relevant engineering units ALARM DELAY The alarm will not trigger until the PV has been in the alarm region for m...

Page 12: ...m delay is 5 s and the maximum 3600 s DISCRETE ACTIVE LEVEL SELECT The function of the discrete input dISc is to operate as a remote clear button press i e you can use this to reset the totals remotely This menu item selects whether the clear function is executed when the discrete is high 24 V ACtHI or low 0 V ACtLO MENU ACCESS PASSCODE When accessing the menus from Run mode the user is prompted f...

Page 13: ...IP CAL IS DISPLAYED The input calibrated data has been Re input calibration data If the error is corrupted still present replace the unit TOTAL DISPLAY AFTER Total has increased above the Press all three front panel keys together READING HIGH NOW displayed 6 low digits of the total and check the 6 high total digits SHOWS A LOW VALUE 15 0 FAULT FINDING Smart In Head Temperature Transmitters DIN Rai...

Reviews: