background image

18

ADJUSTMENT PROCEDURE

INITIAL START-UP

A minimum gas supply pressure of 5.0" (1.25 kPa) W.C. on the SUF 120 and
240 or (4.5" or 1.12 kPa) on SUF 150 and 199 for natural gas (11.0" or 2.74
kPa  W.C. for L.P. Gas) is required before making any adjustment to the gas
control pressure regulator Attempts to adjust the regulator during periods
of low gas supply pressure could result in overfiring of the heater when
the gas supply pressure returns to normal.

1. Check gas line pressure with a manometer.
2. Check manifold pressure (see Table 4, page 20) using a pressure

gauge (manometer) connected to the manifold pressure tap on the
gas control valve, (Figure 15).

If full rate adjustment is required, remove cover screw from top of the
gas control valve, (Figure 15).

Using a small screwdriver, turn adjusting screw clockwise 

 to increase

or counterclockwise 

 to decrease gas pressure to obtain 4.0" (1 kPa)

on SUF 120 and 240 (3.5" or .87  kPa on SUF 150 and 199) for natural gas
(10.0" or 2.5  kPa W.C. for L.P. Gas)  Water Column.

3

. Cycle the burner on and off several times to check its operation.

4. Check the operation of the limit and operating controls.
5. Check the vent system seams and joints and ensure that there is no

discharge of flue products into the room.

6. Check the input rate:
For appliance installation locations with elevations above 2000 feet
(610 m) refer  to HIGH ALTITUDE INSTALLATIONS section of this manual.

a. Attach a pressure gauge (manometer) to the manifold pressure tap

(Figure 15) and refer to Table 4, page 20 for correct pressure.

b. Use this formula to “clock” the meter. Be sure other gas consuming

appliances are not operating during this interval.
3600  

X  H  =  Btuh

T

Should it be necessary to adjust the gas pressure to the burner, to obtain
the full input rate, the steps below should be followed:

T = Time in seconds to burn 1 cubic foot of gas. (With a stopwatch read

the gas meter and measure the amount of time required for the
heater to consume 1 cubic foot of gas.)

H = Heating value of gas (in Btu’s per cubic foot of gas).
Btuh = Actual heater input rate, in Btuh.

EXAMPLE:  (Using SUF- 199 heater)

T = 18.9 seconds
H = 1050 Btu/ft.

3

BTUH = ?

For high altitude installations, compare result to the derated input
required for the elevation at the installation location.

c. Remove the pressure regulator cover screw (Figure 16) and adjust

the pressure by turning the adjusting screw with a small
screwdriver. Do not exceed 4.0" (1 kPa) on SUF 120 and 240
(3.5" [.87  kPa] on SUF 150 and 199) Water Column.

 Clockwise to increase gas pressure and input rate.

Counterclockwise to decrease gas pressure and input rate.

d. “Clock” the meter as in step (b) above.
e. Repeat steps (c) and (d) until the specified input rate is achieved.
f . Turn the manual gas valve to “OFF”. Replace the pressure regulator

cover screw. Remove the pressure gauge or manometer from the
manifold pressure tap. Replace the set screw in the manifold pressure
tap.  If the gas pressure regulator cannot be adjusted to give the full
input rating with sufficient gas pressure at the valve, check to ensure
the unit is equipped with the correct orifice.

PRIOR TO START UP

REQUIRED ABILITY

INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY
EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIELD
INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS SUPPLY AND
ELECTRICAL WORK ARE REQUIRED.

Before attempting start-up, thoroughly study and familiarize yourself with

the exact sequence of operation and all other details on the specific heater
being used.

The power burner is equipped with an ignition system which automatically
sequences prepurge and ignition, senses and ignites main burner flame
and sequences burner operation. Heater is equipped with an ignition control
which locks out after three unsuccessful ignition attempts. Familiarize
yourself with the sequence of operation of this unit prior to start-up.

Be certain that the water heater is full of water, that air is purged from all
lines, there are no leaks (gas and water), and all inlet water lines are open.

The following test equipment should be on hand (all test equipment must be
acclimated to ambient temperature before calibration and use.)

– Two U-tube manometers or calibration 0-10" (0-2.5kPa) and 0-35"
 (0-8.7 kPa) W.C. pressure gauges.

Attach a gas pressure gauge or manometer to the upstream side of
main gas cock and a gas pressure gauge or manometer to the manifold
pressure tap (see Figure 15).

You are now ready to begin the burner start-up procedure.

OPERATING INSTRUCTIONS

IMPORTANT

IT IS RECOMMENDED THAT A QUALIFIED SERVICE TECHNICIAN PERFORM
THE INITIAL FIRING OF THE HEATER. AT THIS TIME THE USER SHOULD ASK
THE TECHNICIAN ANY QUESTIONS IN REGARD TO THE OPERATION AND
MAINTENANCE OF THE UNIT.

 

CAUTION

BEFORE PROCEEDING WITH THE OPERATION OF THE UNIT, MAKE SURE
HEATER AND SYSTEM ARE FILLED WITH WATER AND ALL AIR IS EXPELLED
FROM HEATER AND PIPING.

NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED
WITH WATER AND A TEMPERATURE AND A PRESSURE RELIEF VALVE IS
INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER. DO NOT
ATTEMPT TO OPERATE HEATER WITH COLD WATER INLET VALVE CLOSED.

FILLING:

1. Close the heater drain valve.
2. Open a nearby hot water faucet to permit the air in the system to

escape.

3. Fully open the cold water inlet pipe valve allowing the heater and

piping to be filled.

4. Close the hot water faucet as water starts to flow.
5. The heater is ready to be operated.

THE MAIN MANUAL GAS SHUT-OFF VALVE MUST HAVE BEEN CLOSED
FOR AT LEAST FIVE (5) MINUTES. THIS WAITING PERIOD IS AN IMPORTANT
SAFETY STEP. ITS PURPOSE IS TO PERMIT GAS THAT MIGHT HAVE
ACCUMULATED IN THE COMBUSTION CHAMBER TO CLEAR. IF YOU DETECT
GAS AT THE END OF THIS PERIOD, DO NOT PROCEED WITH LIGHTING.
RECOGNIZE THAT GAS ODOR, EVEN IF IT SEEMS WEAK, MAY INDICATE
THE PRESENCE OF ACCUMULATED GAS SOMEPLACE IN THE AREA WITH A
RISK OF FIRE OR EXPLOSION. SEE THE FRONT PAGE FOR STEPS TO BE
TAKEN.

DO NOT USE THIS HEATER IF ANY PART HAS BEEN UNDER WATER.
IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE
HEATER AND TO REPLACE ANY PART OF THE CONTROL SYSTEM AND
ANY GAS CONTROL WHICH HAS BEEN UNDER WATER.

LIGHT THE UNIT IN ACCORDANCE WITH THE OPERATING INSTRUCTIONS
LABEL ATTACHED TO THE HEATER.

THESE INSTRUCTIONS ARE REPEATED IN THE LIGHTING AND OPERATING
LABEL ILLUSTRATION ON PAGE 20 IN THIS MANUAL.

3600 

X 1050 = 199,900 Btuh (59 Kw)

18.9

Summary of Contents for SUF 100 150NE

Page 1: ...any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation...

Page 2: ...SI Z21 10 3 CSA 4 3 as an automatic circulating tank water heater and automatic storage water heaters Detailed installation diagrams are found in this manual These diagrams will serve to provide the i...

Page 3: ...ON 29 TROUBLESHOOTING 29 30 REPLACEMENTPARTS 30 LIMITED WARRANTY 31 FEATURES IMPORTANT ITIS REQUIREDTHATAQUALIFIED SERVICETECHNICIAN PERFORM THE INITIALFIRING OF THE HEATER ATTHIS TIME THE USER SHOULD...

Page 4: ...MAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLY AND ELECTRICAL WORKARE REQUIRED INSULATION BLANKETS Insulation blankets available to the general public for external use on gas water h...

Page 5: ...d it is recommended that a suitable drain pan adequately drained be installed under the appliance Water heater life depends upon water quality water pressure and the environment in which the water hea...

Page 6: ...t system must terminate so that proper clearances are maintained as cited in local codes or the latest edition of the ANSI Z223 1 NFPA 54 1 Do not terminate the exhaust vent terminal over public area...

Page 7: ...7 FIGURE 5 NOTE SUF 100 240 USES TEE ON AIR INTAKE TERMINAL DIRECT VENT HORIZONTAL VENT FIGURE 6...

Page 8: ...y air inlet into building 4 The manufacturer also recommends the vent system terminations not be installed closer than 3 91cm from an inside corner of an L shaped structure And not less than 1 30 5 cm...

Page 9: ...de of the line This will allow the vent pipe to easily slide through the opening The resulting gap will be covered by the vent terminal cover plates Repeat this step on the inside wall if necessary 4...

Page 10: ...nt pipes to be inserted through the roof 2 Drill a pilot hole approximately 1 4 6 mm outside of the marked circle This pilot hole is used as a starting point for a saws all or sabre saw blade Cut arou...

Page 11: ...ivalent feet 15 2 m of three inch PVC vent pipe on the intake Also verify that the intake and intake vent terminal is free of obstructions that may prevent air from entering the unit 3 4 inch PVC may...

Page 12: ...HR FEET 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 10 175 360 680 1400 2100 3960 6300 11000 23000 20 120 250 485 950 1460 2750 4360 7700 15800 30 97 200 375 770 1180 2200 3520 6250 12800 40 82 170 320 660 990...

Page 13: ...heater as well as the requirements of all other gas fired equipment supplied by the meter If the gas meter is too small ask the gas company to install a larger meter having adequate capacity GAS PRES...

Page 14: ...WITH WATER NOTE This controller is Polarity Sensitive If the Hot and Neutral Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit WATER LINE CONNE...

Page 15: ...tep 2 and repeat the entire operating cycle SELF DIAGNOSTIC CONTROLLER A green LED is mounted on the Main Control Board to indicate line voltage polarity is properly connected The green LED is mounted...

Page 16: ...ame probe faulty 4 Replace flame probe 5 Gas shut off 5 Turn on gas supply 6 Clogged gas valve 6 Replace gas valve 7 Faulty gas valve 7 Replace gas valve 8 Defective control 8 Replace control 9 Burner...

Page 17: ...trol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe PossibleCause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring short...

Page 18: ...heck to ensure the unit is equipped with the correct orifice PRIOR TO START UP REQUIRED ABILITY INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRESABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN...

Page 19: ...19 FORYOUR SAFETYREAD BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life...

Page 20: ...ING SUF HEATERSARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 6500 FEET INSTALLATIONSABOVE 6500 FEET MAY REQUIREREPLACEMENTOFTHEBURNERORIFICE CALLTHETECHNICAL CENTER 800 527 1953 FOR R...

Page 21: ...ished flushing 4 Turn on the heater electrical disconnect switch DRAINING The heater must be drained if it is to be shut down and exposed to freezing temperatures Maintenance and service procedures ma...

Page 22: ...ration and a tank explosion In areas with poor water conditions it may be necessary to inspect the T P valve more often than every three years CAUTION BEFORE MANUALLY OPERATING THE VALVE MAKE SURE THA...

Page 23: ...T WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALLINACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVEORWATERMETERWITH CHECK VALVE PROVISIONS...

Page 24: ...R TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD...

Page 25: ...KIT SPECIFICATIONS PAGE28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FORTHERMALEXPANSION OF WATER IN THE HOT WATER SYSTEM MU...

Page 26: ...ECTCIRCULATINGLINEOF180 F 82 C ORBOOSTEDWATER IF USED TO INLETWATER LINETO BOOSTER INSTALLINACCORDANCE WITH LOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUI...

Page 27: ...HETANK NOTE4 IFTEMPEREDWATERISRECIRCULATED RETURNLINESHOULD BE CONNECTEDATPOINTA DANGER TEMPERATURESETTINGSHOULDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEE WATERTEMPERATURE CONTROLWARNING ON PAGE 3 IF HIG...

Page 28: ...heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kit...

Page 29: ...SUSPECTED 1 Check to see if the water heater drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the he...

Page 30: ...5 kPa W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 5 0 1 25 kPa W C for SUF 120 240 or 4 5 1 1 kPa W C for SUF 150 199 or for L P Gas 11 0 2 74 kPa W C...

Page 31: ...31...

Page 32: ...32 500 LIndahl Parkway Ashland City TN 37015 Phone 1 800 821 2017 Fax 1 800 644 9306 www stateind com...

Reviews: