background image

15

OPERATION

SEQUENCE OF OPERATION

Typical Control/Appliance Operating Sequence

1. When the control is initially powered, it enters a test mode and will

display the current software revision (example "104") for approximately
2 seconds, then "88.8" and all the LED's will illuminate for approximately
2 seconds. At this point, the control is in the idle mode and will display
the actual tank temperature.

2. If the control determines the actual water temperature inside the tank is

below the programmed temperature setpoint less one half the differential,
a call for heat is activated.

3. The control then performs selected system diagnostic checks. This

includes confirming the proper state of the air switch, ignitor, gas valve,
flame sense rod, and ECO limit device.

4. If all checks are successfully passed, the combustion blower is energized

for the pre-purge cycle.

5. When the pre-purge cycle is complete, power is applied to the ignitor

element for the ignitor warm-up period (blower should continue to run).

6. During the ignitor warm-up period, the control will sense ignitor current.

If ignitor current is within the specified range, the controller will energize
(open) the gas valve at the end of the ignitor warm-up period, allowing
gas to enter the burner chamber. If ignitor current is not within the
specified range, the control will not energize the gas valve, and the
control will return to Step 2 of the process. (See section below:
Appliance Ignition Failure).

7. After energizing the gas valve, the control will keep the ignitor on for a

short predetermined time period, then remove power to the ignitor.

8. After an additional 1 second, the control will monitor the flame sense

probe to confirm a flame is present. If a flame is not verified within this
time period, the controller will immediately de-energize (close) the gas
valve, and return to step two of the process. (See section below:
Appliance Ignition Failure).

9. If a flame is confirmed, the control will enter the heating mode where it

will continue heating the tank water until the setpoint temperature plus
one half the differential is reached. At this point, the gas valve is closed
and the control enters the post-purge cycle.

10.The combustion blower will run for the duration of the post purge cycle

to purge the system of all combustion  gases. When the post purge
cycle is complete, the blower is de-energized and will coast to a stop.

11. The control will now enter the idle state while continuing to monitor the

internal tank water temperature and the internal state of the controller. If
the temperature drops below the setpoint value less one half the
differential, the control will automatically return to Step 2 and repeat the
entire operating cycle.

SELF DIAGNOSTIC CONTROLLER

A green LED is mounted on the Main Control Board to indicate line voltage
polarity is properly connected. The green LED is mounted next to connector
CN1 (Line input connection). When 120 VAC input power is properly
connected to the Main Control Board, the green LED will illuminate. If an
error is made when connecting 120 VAC input power, this LED will not light.
Improperly connecting the input power may result in a false sensor failure.

The 24 VAC circuitry is protected with a 3 amp auto fuse. If the fuse opens,
the LED display and discrete LED's on the Display Board assembly will not
illuminate. The recommended fuse replacement part is Littlefuse p/n 257003
automotive fuse. Repeated failure of the fuse is an indication of possible
damage to the Main Control Board. If repeated fuse failure occurs, return
the Control Board for service.

Under normal operating conditions, should the ignitor current fall out of
specification or the gas fail to light at the burner during the first trial for
ignition, the control will perform two (2) more ignition trials prior to entering
a lockout state. Note that each subsequent ignition trial will not occur
immediately. After a failed trial for ignition, the controller will remove all
power from the blower, gas valve, and ignitor and return to the call for heat
state. If a call for heat is activated, the controller will energize the combustion
blower for the pre-purge cycle, and again activate the ignitor to complete its
warm-up period. After the warm-up period, the gas valve is opened, ignitor
power removed, and the control will again check for flame.

If ignition is sensed during any one of these trials, normal operation will
resume. If ignitor current should fall out of specification or flame is not
sensed after the third ignition trial, the control will automatically enter a
lockout state ("Loc" displayed on the Display Board) and the ignitor or gas
valve LED on the Display Board will flash. The lockout state is manually
reset by momentarily pressing the push-button on the Display Board. If a
manual reset does not occur within a one hour time period, the controller
will automatically reset the lockout condition and provided the call for heat
still exists, will attempt another ignition sequence.

FIGURE 18

GAS VALVE LED FLASHING

FIGURE 17

14. Tubing-Pressure
15. Tubing-Pressure
17. Switch-On/Off
18. Low Gas Pressure Switch

(SUF 120 and 240 Only).

19. Bocked Inlet Switch
20. Wire Assembly-Air

Flow Switch

ITEM DESCRIPTION

 

 1. Transformer

  2. Control Board & Cable Ass'y
  3. E.C.O./Temperature  Probe
  4. Blower Proving Air Switch
  5. Low  Voltage  Cable Assembly
  6. Line  Voltage  Cable Assembly
  7. Blower/Motor  Assembly
  8. Igniter  Assembly
10. Control Display Board
11.

Blocked Outlet Exhaust Switch

12. Lower Temperature Probe
13. Wire Assembly-Gas Pressure

Switch

Summary of Contents for SUF 100 150NE

Page 1: ...any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation...

Page 2: ...SI Z21 10 3 CSA 4 3 as an automatic circulating tank water heater and automatic storage water heaters Detailed installation diagrams are found in this manual These diagrams will serve to provide the i...

Page 3: ...ON 29 TROUBLESHOOTING 29 30 REPLACEMENTPARTS 30 LIMITED WARRANTY 31 FEATURES IMPORTANT ITIS REQUIREDTHATAQUALIFIED SERVICETECHNICIAN PERFORM THE INITIALFIRING OF THE HEATER ATTHIS TIME THE USER SHOULD...

Page 4: ...MAN IN THE FIELD INVOLVED PLUMBING AIR SUPPLY VENTING GAS SUPPLY AND ELECTRICAL WORKARE REQUIRED INSULATION BLANKETS Insulation blankets available to the general public for external use on gas water h...

Page 5: ...d it is recommended that a suitable drain pan adequately drained be installed under the appliance Water heater life depends upon water quality water pressure and the environment in which the water hea...

Page 6: ...t system must terminate so that proper clearances are maintained as cited in local codes or the latest edition of the ANSI Z223 1 NFPA 54 1 Do not terminate the exhaust vent terminal over public area...

Page 7: ...7 FIGURE 5 NOTE SUF 100 240 USES TEE ON AIR INTAKE TERMINAL DIRECT VENT HORIZONTAL VENT FIGURE 6...

Page 8: ...y air inlet into building 4 The manufacturer also recommends the vent system terminations not be installed closer than 3 91cm from an inside corner of an L shaped structure And not less than 1 30 5 cm...

Page 9: ...de of the line This will allow the vent pipe to easily slide through the opening The resulting gap will be covered by the vent terminal cover plates Repeat this step on the inside wall if necessary 4...

Page 10: ...nt pipes to be inserted through the roof 2 Drill a pilot hole approximately 1 4 6 mm outside of the marked circle This pilot hole is used as a starting point for a saws all or sabre saw blade Cut arou...

Page 11: ...ivalent feet 15 2 m of three inch PVC vent pipe on the intake Also verify that the intake and intake vent terminal is free of obstructions that may prevent air from entering the unit 3 4 inch PVC may...

Page 12: ...HR FEET 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 10 175 360 680 1400 2100 3960 6300 11000 23000 20 120 250 485 950 1460 2750 4360 7700 15800 30 97 200 375 770 1180 2200 3520 6250 12800 40 82 170 320 660 990...

Page 13: ...heater as well as the requirements of all other gas fired equipment supplied by the meter If the gas meter is too small ask the gas company to install a larger meter having adequate capacity GAS PRES...

Page 14: ...WITH WATER NOTE This controller is Polarity Sensitive If the Hot and Neutral Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit WATER LINE CONNE...

Page 15: ...tep 2 and repeat the entire operating cycle SELF DIAGNOSTIC CONTROLLER A green LED is mounted on the Main Control Board to indicate line voltage polarity is properly connected The green LED is mounted...

Page 16: ...ame probe faulty 4 Replace flame probe 5 Gas shut off 5 Turn on gas supply 6 Clogged gas valve 6 Replace gas valve 7 Faulty gas valve 7 Replace gas valve 8 Defective control 8 Replace control 9 Burner...

Page 17: ...trol problem 2 Water in tank above freezing 2 Temperature probe out of tolerance replace temp probe PossibleCause Remedy 1 Water in tank is low probe 1 Fill tank immersed in steam 2 Probe wiring short...

Page 18: ...heck to ensure the unit is equipped with the correct orifice PRIOR TO START UP REQUIRED ABILITY INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRESABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN...

Page 19: ...19 FORYOUR SAFETYREAD BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life...

Page 20: ...ING SUF HEATERSARE CERTIFIED FOR USE WITHOUT MODIFICATION FOR ALTITUDES UP TO 6500 FEET INSTALLATIONSABOVE 6500 FEET MAY REQUIREREPLACEMENTOFTHEBURNERORIFICE CALLTHETECHNICAL CENTER 800 527 1953 FOR R...

Page 21: ...ished flushing 4 Turn on the heater electrical disconnect switch DRAINING The heater must be drained if it is to be shut down and exposed to freezing temperatures Maintenance and service procedures ma...

Page 22: ...ration and a tank explosion In areas with poor water conditions it may be necessary to inspect the T P valve more often than every three years CAUTION BEFORE MANUALLY OPERATING THE VALVE MAKE SURE THA...

Page 23: ...T WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALLINACCORDANCE WITH LOCAL CODES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVEORWATERMETERWITH CHECK VALVE PROVISIONS...

Page 24: ...R TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD...

Page 25: ...KIT SPECIFICATIONS PAGE28 CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FORTHERMALEXPANSION OF WATER IN THE HOT WATER SYSTEM MU...

Page 26: ...ECTCIRCULATINGLINEOF180 F 82 C ORBOOSTEDWATER IF USED TO INLETWATER LINETO BOOSTER INSTALLINACCORDANCE WITH LOCALCODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUI...

Page 27: ...HETANK NOTE4 IFTEMPEREDWATERISRECIRCULATED RETURNLINESHOULD BE CONNECTEDATPOINTA DANGER TEMPERATURESETTINGSHOULDNOTEXCEEDSAFETEMPERATUREAT FIXTURES SEE WATERTEMPERATURE CONTROLWARNING ON PAGE 3 IF HIG...

Page 28: ...heating and storage potential of the system cannot be achieved Plus the units with the higher water flow may have a shortened life Unions shown in piping diagrams are not included in the manifold kit...

Page 29: ...SUSPECTED 1 Check to see if the water heater drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the he...

Page 30: ...5 kPa W C or lower than the minimal gas supply pressure as shown in Table 4 that is for Natural Gas 5 0 1 25 kPa W C for SUF 120 240 or 4 5 1 1 kPa W C for SUF 150 199 or for L P Gas 11 0 2 74 kPa W C...

Page 31: ...31...

Page 32: ...32 500 LIndahl Parkway Ashland City TN 37015 Phone 1 800 821 2017 Fax 1 800 644 9306 www stateind com...

Reviews: