State Water Heaters SBL85275NE Service Handbook Download Page 12

10

Servicing should only be performed by a Qualified Service Technician

7.  Remove the 4 brass nuts and 4 lockwashers holding the flange plate to the skirt ring flange.
8.  Pull the adapter tube/flange plate/burner assembly out of the combustion chamber. Take care not to 

damage the spark igniter or flame sensor during the removal process.

9.  Clean the flange plate and skirt ring flange surfaces to remove any portions of the old skirt ring flange 

gasket.

10. Support the adapter tube/flange plate/burner assembly in a vertical position with the burner extending 

downward.

11. Remove the 3 brass locknuts holding the adapter tube to the flange plate.
12. Separate the adapter tube from the flange plate.
13. Clean the adapter tube and flange plate surfaces removing any portions of the old burner gasket. 

Dispose of the old burner gasket.

14. Remove the burner from the flange plate taking care not to damage the spark igniter and flame sensor.
15. Insert the new burner into the flange plate and align the notch in the burner flange with the tab in the 

flange plate.

16. Install the new burner gasket over the three studs extending from the flange plate.
17. Install the adapter tube on the flange plate with the 3 brass locknuts. Torque the nuts to 60 in.lb.
18. Install the new skirt ring flange gasket on the flange plate.
19. Insert the adapter tube/flange plate/burner assembly into the combustion chamber and engage the 4 

studs through the mounting holes/slots in the flange plate. Install 4 lockwashers and 4 brass nuts on the 

studs and torque to 15 ft.lb.

20. Reinstall the blower and silicone gasket on the adapter tube flange using the 4 fasteners. Torque the 

fasteners to 20 ft.lb.

21. Reconnect the gas valve to the blower assembly at the gas valve flange. Make sure the o-ring is 

properly positioned in the flange groove before tightening the 4 retaining screws.

22. Reconnect the spark ignition cable and ground wire plus the flame sensor wire at their connection 

points on the flange plate.

23. Reconnect the vacuum and pressure tubes if removed in step 3.
24. Check that all gas connections and fasteners are tight.
25. Turn on the gas supply and electricity to water heater. Turn on the water heater with the on-off switch 

and allow it to ignite and run. While running, check the gas valve flange and the gasketed joints in the 

combustion system for leaks.

Summary of Contents for SBL85275NE

Page 1: ...CING SHOULD ONLY BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN Service Handbook COMMERCIAL GAS WATER HEATERS FOR MODELS SBL85275NE A SBL85310NE A SBL85366NE A SBL85390NE A ULTRA LOW NOx SERIES 104 IN...

Page 2: ......

Page 3: ...OF OPERATION FLOW CHART 17 SEQUENCE OF OPERATION FLOW CHART 18 LIGHTING AND OPERATING LABEL 19 TROUBLESHOOTING 20 CONTROLS OVERVIEW CONTROL BOX ASSEMBLY 21 PRESSURE SWITCHES ALL MODELS 22 HIGH LIMIT...

Page 4: ...Qualified Agency Any individual firm corporation or company that either in person or through a representative is engaged in and is responsible for 1 the installation testing or replacement of gas pip...

Page 5: ...s required for testing pressure switches and can replace a gas pressure gauge draft gauge or slack tube manometer for checking gas pressure UEi model EM200 or equivalent Water pressure gauge w lazy ha...

Page 6: ...ration 3 Check the operation of the limit and operating controls 4 Check the vent system seams and joints and ensure that there is no discharge of flue products into the room 5 Check the input rate Su...

Page 7: ...the installed space The vent system on one or more gas fired appliances can experience down drafts due to the outdoor air pressure being greater than the ambient air pressure in the installed space Wh...

Page 8: ...ommunicate with the outdoors and must communicate through a vertical or horizontal duct to the outdoors or spaces crawl or attic that freely communicate with the outdoors and must have a minimum free...

Page 9: ...ue to thermal expansion Thermal expansion can cause premature tank failure leakage This type of failure is not covered under the limited warranty Thermal expansion can also cause intermittent Temperat...

Page 10: ...ef Valve Upper Thermostat Probe ECO Lower Thermostat Probe Control Box Assembly Drain Valve Combustion Blower Burner Assembly Gas Control Valve Clean Out Cover The Eliminator Exhaust Vent Combustion A...

Page 11: ...rom the blower at the gas valve flange by unscrewing the 4 retaining screws Keep the o ring that is located in the flange groove This o ring seals the flange to the gas valve 5 Remove the 4 fasteners...

Page 12: ...ew burner gasket over the three studs extending from the flange plate 17 Install the adapter tube on the flange plate with the 3 brass locknuts Torque the nuts to 60 in lb 18 Install the new skirt rin...

Page 13: ...The spark gap between the spark rod and grounding rod is 1 8 FLAME SENSOR This water heater is equipped with a flame sensor The flame sensor senses flame by passing a small electric current through t...

Page 14: ...low Figure and Table In all installations the minimum combustible clearances from vent piping shall be 6 15 2 cm Vent piping passing through a combustible wall or ceiling must be a continuous run no j...

Page 15: ...s the required clearances for venting units using natural draft venting The vent must extend at least 3 feet above the highest point where it passes through a roof of a building and at least 2 feet hi...

Page 16: ...0 1 Ft 8 8 8 7 7 6 6 310 000 2 Ft 8 8 8 7 7 7 6 6 310 000 3 Ft 8 8 8 7 7 7 6 6 Number of Heaters Combined Input in Thousands of Btu hr Manifold and Common Vent Diameters Inches 2 620 000 12 10 10 9 9...

Page 17: ...Diameter Inches 0 6 6 6 6 5 5 5 5 2 7 7 7 6 6 6 6 5 4 7 NA NA NA NA NA NA NA 5 NA 7 7 6 6 6 6 5 6 7 NA NA NA NA NA NA NA 8 NA 7 NA NA NA NA NA NA 10 NA NA 7 6 6 6 6 6 15 NA NA NA 7 6 6 6 6 20 NA NA NA...

Page 18: ...or does not detect proper flame the Ignition Control shuts off the Gas Valve and allows the Blower to purge the unit At that time the Ignition Control restarts with step 6 It will try and ignite the m...

Page 19: ...17 Servicing should only be performed by a Qualified Service Technician DIAGNOSTIC SEQUENCE OF OPERATION FLOW CHART...

Page 20: ...18 Servicing should only be performed by a Qualified Service Technician SEQUENCE OF OPERATION FLOW CHART...

Page 21: ...t causing property damage personal injury or loss of life BEFORE OPERATING ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINES A B This appliance does not have a pilot It is equipped...

Page 22: ...ency Check gas input If incorrect check for inlet air blockage and or flue gas exhaust blockage Water temperature too hot Thermostat set too high Set thermostat to a lower setting Rumbling Sediment ac...

Page 23: ...d by a Qualified Service Technician CONTROLS OVERVIEW CONTROL BOX ASSEMBLY Variable Frequency Drive Digital Thermostat Ignition Control Blocked Outlet Switch Blower Prover Switch ON OFF Switch High Sp...

Page 24: ...ation of the unit The switches are wired to the Ignition control in series It is important to understand the purpose of each switch PRESSURE SWITCHES PRESSURE SWITCHES Model Setpoint WC Tolerance WC B...

Page 25: ...pen on a rise in pressure HIGH LIMIT SWITCH DIGITAL THERMOSTAT The digital thermostat contains the high limit energy cut out switch The high limit switch interrupts burner gas flow should the water te...

Page 26: ...ut Out has opened Check for excessively hot water 203 F or higher Check the resistance of the temperature probes and continuity of the high limit ECO No power Check the breaker Tank is at a set temper...

Page 27: ...uity is indicated ZERO 0 0 Resistance Opens at 203 F closes at 193 F If water is below 193 F continuity is correct Continuity is not present meter reads 0 L Replace ECO sensor if water temperature is...

Page 28: ...Temperature Probe continuity check Red wire to red wire Turn supply power Off for this test IF THEN Test indicates no continuity Replace probe Continuity is indicated Probe should be okay also verify...

Page 29: ...inuity check Red wire to red wire Turn supply power Off for this test IF THEN Test indicates no continuity Replace probe Continuity is indicated Probe should be okay also verify Ohms resistance for wa...

Page 30: ...o ignite the burner three times before lockout The control waits 15 minutes before trying again to ignite the burner This is a continuous cycle This is a 24 VAC ignition control The microprocessor cir...

Page 31: ...VFD speed signals are de energized immediately FAILURE TO LIGHT LOCKOUT MULTI TRIAL CONTROL Should the burner fail to light or if flame is not detected during the first trial for ignition period the g...

Page 32: ...ad control check LED for steady on or flashing code see above Table d Pressure switch contacts did not close Tubing or wire off pressure switches 2 Thermostat on no spark a Miswired b No 24V AC power...

Page 33: ...lower motor The VFD receives a signal from the thermostat and ignition control that instructs the VFD to transmit the proper frequency to the blower to produce the proper blower speed and proper input...

Page 34: ...rive Line supply is at the top of the drive the motor power supply is at the bottom of the drive VFD BLOWER SPEED AND FREQUENCY READINGS The logic inputs for the VFD are sent from the thermostat and i...

Page 35: ...33 Servicing should only be performed by a Qualified Service Technician WIRING DIAGRAM SBL85275NE A THRU SBL85390NE A...

Page 36: ...link of www statewaterheaters com for a listing of available Service Handbooks For additional information contact State Water Heaters 500 Tennessee Waltz Parkway Ashland City TN 37015 1 800 527 1953 w...

Reviews: