background image

23

gas piping

Contact  your  local  gas  service  company  to  ensure  that  adequate 

gas service is available and to review applicable installation codes 

for your area.
Size the main gas line in accordance with Table 8. The figures shown 

are for straight lengths of pipe at 0.5 in. W.C. pressure drop, which is 

considered normal for low pressure systems. Note: Fittings such as 

elbows, tees and line regulators will add to the pipe pressure drop. 

Also refer to the latest version of the National Fuel Gas Code.
Schedule  40  Steel  or  Wrought  Iron  Pipe  is  the  preferred  material 

for  the  gas  line  of  this  water  heater.  It  is  imperative  to  follow  the 

sizing  recommendations  in  the  latest  version  of  the  National  Fuel 

Gas Code if Corrugated Stainless Steel Tubing (CSST) is used as 

the gas line for this water heater.
The heater is not intended for operation at higher than 14.0" W.C.- 

natural gas, (1/2 pound per square inch gage) supply gas pressure. 

exposure  to  higher  supply  pressure  may  cause  damage  to  the 

gas  valve  which  could  result  in  fire  or  explosion.  If  overpressure 

has  occurred  such  as  through  improper  testing  of  gas  lines  or 

emergency malfunction of the supply system, the gas valve must be 

checked for safe operation. Make sure that the outside vents on the 

supply regulators and the safety vent valves are protected against 

blockage. These are parts of the gas supply system, not the heater. 

Vent blockage may occur during ice storms.

taBle 8 - gas supply pipe lengths (in feet)
maximum equivalent pipe length - natural gas only

Input rate 

(bTu/Hr)

Schedule 40 Steel or Wrought Iron Pipe

1/2"

3/4"

1"

1 1/4"

1 1/2"

120,000

20

70

200

200

200

154,000

10

40

150

200

200

180,000

-

30

100

200

200

199,000

-

30

90

200

200

250,000

-

20

60

200

200

275,000

-

10

50

200

200

310,000

-

10

40

150

200

366,000

-

-

30

100

200

390,000

-

-

20

100

200

Fitting Type*

equivalent length in feet

45°ell

0.7

1.0

1.2

1.6

1.9

90°ell

1.6

2.1

2.6

3.5

4.0

Tee

3.1

4.1

5.2

6.9

8.0

Natural Gas 0.60 Specific Gravity, 0.50" W.C. Pressure Drop

*Screwed Fittings

It is important to guard against gas valve fouling from contaminants 

in the gas ways. Such fouling may cause improper operation, fire or 

explosion.
If copper supply lines are used they must be internally tinned and 

certified for gas service. before attaching the gas line, be sure that 

all gas pipe is clean on the inside.
To trap any dirt or foreign material in the gas supply line, a sediment 

trap must be incorporated in the piping (see Figure 21). The sediment 

trap must be readily accessible and not subject to freezing conditions. 

Install in accordance with recommendations of serving gas suppliers. 

refer to the latest version of the National Fuel Gas Code.
To prevent damage, care must be taken not to apply too much torque 

when attaching gas supply pipe to gas valve inlet.
Apply joint compounds (pipe dope) sparingly and only to the male 

threads of pipe joints. Do not apply compounds to the first two threads. 

use compounds resistant to the action of liquefied petroleum gases.

gas meter size – natural gases only

be sure the gas meter has sufficient capacity to supply the full rated 

gas input of the water heater as well as the requirements of all other 

gas fired equipment supplied by the meter. If gas meter is too small, ask 

the gas company to install a larger meter having adequate capacity.

supply gas regulator

The minimum gas supply pressure must not be less than 3.5" w.c. 

(0.87 kPa).
Do  not  subject  the  gas  valve  to  inlet  gas  pressures  of  more  than 

14.0” W.C. (3.48 kPa). A supply gas regulator is necessary if higher 

gas pressures are encountered. See Gas Pressure requirements 

and Supply Gas regulator sections on page 12.
1. Supply gas regulators must be rated above the input btu/hr rating 

of the water heater they supply.

2. Supply gas regulators shall have inlet and outlet connections not 

less than the minimum supply gas line size for the water heater 

they supply. See Table 8. on page 23.

gas piping and sediment trap installation

figure 21.

gas line leak testing

Fire and Explosion Hazard

Leak test before placing the water

heater in operation.
Disconnect gas piping and main gas

shutoff valve before leak testing.
Install sediment trap in accordance

with NFPA 54.

Use joint compound or Teflon tape

compatible with propane gas.

Any time work is done on the gas supply system perform a leak test 

to avoid the possibility of fire or explosion.
1. For  test pressures  exceeding  1/2  psi  (3.45  kPa)  disconnect  the 

water heater and its Main Gas Shutoff Valve from the gas supply 

piping system during testing, see Figure 21. The gas supply line 

must be capped when disconnected from the water heater.

2. For test pressures of 1/2 psi (3.45 kpa) or less, the appliance need 

not be disconnected, but must be isolated from the supply gas line 

by closing the Main Gas Shutoff Valve during testing.

3. Coat all supply gas line joints and connections upstream of  the 

water  heater  with  a  non-corrosive  soap  and  water  solution  to 

test for leaks. bubbles indicate a gas leak. Do not use matches, 

candles, flame or other sources of ignition for this purpose.

4. repair any leaks before placing the water heater in operation.

purging

Gas line purging is required with new piping or systems in which air 

has entered.
Purging should be performed per the current edition of NFPA 54 the 

National Fuel Gas Code.

Summary of Contents for SBL85 275NE

Page 1: ...ine or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any...

Page 2: ...ditions 32 Operational Conditions 32 Troubleshooting 33 Water Piping Diagrams 34 Notes 50 Limited Warranty 51 Table Of Contents Safe Installation Use and Service 3 APPROVALS 3 General Safety Informati...

Page 3: ...ate of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State...

Page 4: ...ation Contact a qualified installer or service agency for installation and service Excessive gas pressure to gas valve can cause serious injury or death Do not use water heater with any gas other than...

Page 5: ...ter system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow There should be no smoking or open flame near the faucet at...

Page 6: ...ting gas supply and electrical supply are required in addition to electrical testing skills when performing service ANSI Z223 1 2012 Sec 3 3 85 Qualified Agency Any individual firm corporation or comp...

Page 7: ...cause poor performance of the heater and can significantly reduce outlet water temperatures during heavy draws Note The Hydrocannon may have 1 3 or 7 cross tubes Figure 2 High Limit Switch The digital...

Page 8: ...Kg 900 lbs 408 Kg Table 2 Recovery Capacities based on 82 efficiency Input BTUH Input KW U S Gal Liters Eff U S Gallons Hr and Liters Hr at TEMPERATURE RISE INDICATED Deg F 36 40 50 54 60 70 72 80 90...

Page 9: ...maintained from serviceable parts The units are approved for installation with side rear and ceiling clearances as indicated below Table 4 Minimum Clearances to Combustible or non combustible construc...

Page 10: ...n labels from the manufacturer for placement on the blanket directly over the existing labels DO inspect the insulation blanket frequently to make certain it does not sag thereby obstructing combustio...

Page 11: ...MP WIRING DIAGRAM STORAGE TANK OR BUILDING RECIRCULATION FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE STORAGE TANK OR CIRCULATING LOOP RETURN LINE CIRC PUMP MOTOR L1 HOT L2 NEUTRAL 120 VAC POWE...

Page 12: ...pressure and with all gas burning equipment running at maximum rate dynamic pressure The gas supply pressure must be stable within 1 5 W C 0 37 kPa from static to dynamic pressure to provide good perf...

Page 13: ...ge 20 and Water Piping Diagrams on page 34 Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized temper...

Page 14: ...not intended for the constant relief of thermal expansion A properly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Systems and Ther...

Page 15: ...tand instruction manual For safe operation an adequate supply of fresh uncontaminated air for combustion and ventilation must be provided An insufficient supply of air can cause recirculation of combu...

Page 16: ...Figure 15 Alternatively a single permanent opening commencing within 12 inches 300 mm of the top of the enclosure shall be provided See Figure 14 The water heater shall have clearances of at least 1 i...

Page 17: ...aggregate input rating of all appliances installed in the enclosure Each opening shall not be less than 100 square inches 645 cm2 Outdoor Air Through Two Vertical Ducts The illustrations shown in thi...

Page 18: ...HNICAL DATA VENTING MODEL SBL95 199NE Input 199 000 Btu hr Total Vent Height Feet Vent Connector Size 6 inches 6 8 10 15 20 30 50 100 Input Btuh hr Rise Vent Connector Diameter Inches 199 000 1 Ft 7 7...

Page 19: ...mon Vent Diameters Inches 2 550 000 10 9 9 8 8 8 7 7 3 825 000 12 12 12 10 9 9 8 8 4 1 100 000 14 14 14 12 12 10 9 9 MODEL SBL85 390NE A Input 390 000 Btu hr Total Vent Height Feet Vent Connector Size...

Page 20: ...installation of the water piping begins 1 Water Temperature Control and Mixing Valves on page 12 2 Dishwashing Machines on page 13 3 Temperature Pressure Relief Valve on page 13 4 Closed Systems and T...

Page 21: ...ing heat to this fitting Do not allow pipe dope to contact the plastic tube during installation Tube Inlet Installation Figure 19 TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES...

Page 22: ...tion AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION The controls of this water heater are polarity sensitive Be certain to properly wire the hot and neut...

Page 23: ...cordance with recommendations of serving gas suppliers Refer to the latest version of the National Fuel Gas Code To prevent damage care must be taken not to apply too much torque when attaching gas su...

Page 24: ...from faucets after extended periods of non use 1 Close the Main Gas Shutoff Valve see Figure 21 on page 23 2 Purge all air from the supply gas line up to the water heater s Main Gas Shutoff Valve 3 W...

Page 25: ...he supply gas regulator as necessary Adjust the supply gas regulator s per the regulator manufacturer s instructions to achieve the required static and dynamic supply gas pressure Multiple Appliance I...

Page 26: ...TO APPLIANCE and call your technician or gas supplier Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell gas...

Page 27: ...Valve Ignition Control maintains spark for up to 4 seconds and monitors Flame Sensor to determine if Burner is lit Does Burner light Ignition Control changes Blower from low speed to high speed after...

Page 28: ...y thermal expansion in a closed system See Closed Water Systems and Thermal Expansion on page 13 The Temperature Pressure Relief Valve is not intended for the constant relief of thermal expansion Temp...

Page 29: ...hismanual 11 Turn on the electrical supply to place the water heater back in operation 12 Turn on the gas supply to the water heater at the Main Gas Shutoff Valve 13 Allow the water heater to complete...

Page 30: ...pening and scrape out any loose deposits of scale or sediment This is an economical way to avoid unnecessary usage of the deliming solution Repeat the opening and closing of the cold water inlet valve...

Page 31: ...itting into the drain valve opening of heater after applying Teflon tape or paste to threads Tighten firmly by hand and use wrench or adjustable pliers to check for secure connection Do not over tight...

Page 32: ...be restarted unless the water temperature is reduced to approximately 120 F 49 C The high limit reset button on the front of the thermostat then needs to be depressed See Figure 2 for the location of...

Page 33: ...blockage and or flue gas exhaust blockage Water temperature too hot Thermostat set too high Set thermostat to a lower setting Rumbling Sediment accumulation on bottom of tank Drain a quantity of water...

Page 34: ...should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TE...

Page 35: ...ostat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP...

Page 36: ...and the storage tank s MULTI FLUE 1 UNIT WITH MIXING VALVE TWO TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BAL...

Page 37: ...mp between the water heater s and the storage tank s MULTI FLUE 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VA...

Page 38: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 39: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 40: ...t should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 41: ...EMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SU...

Page 42: ...VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES C...

Page 43: ...LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING...

Page 44: ...an the Tank Temperature Control MULTI FLUE 3 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT B...

Page 45: ...than the Tank Temperature Control MULTI FLUE 3 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PO...

Page 46: ...RE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED...

Page 47: ...perature Control MULTI FLUE 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPE...

Page 48: ...emperature Control MULTI FLUE 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE T...

Page 49: ...49 Model Dimension A SBL95 199NE 76 SBL85 275NE A 76 SBL85 390NE A 76...

Page 50: ...50 Notes...

Page 51: ...an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an accepta...

Page 52: ...www statewaterheaters com 500 Tennessee Waltz Parkway Ashland City TN 37015 Tech Support 800 527 1953 Parts 800 433 2545 Copyright 2012 State Water Heaters All rights reserved...

Reviews: