The installer may be able to observe and correct certain problems 

which may arise when the unit is put into operation. HOWeVer, 

it  is  recommended  that  only  a  qualified  service  agency,  using 

appropriate test equipment, be allowed to service the heater.
As  preliminary  step,  check  wiring  against  diagram,  check  for 

grounded, broken or loose wires.  Check all wire ends to be sure 

that they are making good contact.

ignition Control system

before  calling  your  qualified  service  agency,  the  following 

checklist  should  be  examined  to  eliminate  obvious  problems 

from those requiring replacement or servicing.
•  Check that “main gas shutoff valve” is fully open and that gas 

service has not been interrupted.

•  Check  electrical  supply  to  the  appliance  for  possible  blown 

(or tripped) fusing or power interruption. Also check the 3 amp 

fuse on the front of the digital thermostat (Fig. 2).

•  Is  the  water  temperature  in  tank  below  the  thermostat  dial 

setting on the appliance thermostat (calling for heat)?

•  It is possible that the high limit (e.C.O.) has functioned to shut 

off  the  appliance.  See  page  7  -  High  limit  Switch  for  reset 

procedure.  Contact  your  service  agent  if  limit  continues  to 

function to shut off appliance. 

and pour the uN•lIMe into the heater.

7.  lower container, you may have to place the container on 

its empty carton to prevent the uN•lIMe from flowing back 

into the container.

8.  let uN•lIMe remain in the heater for 5 minutes and then 

lower the container to the “Drain” Position, see Figure 27.

9.  Deliming activity is indicated by foaming on the surface of the 

uN•lIMe. If there is deliming activity, repeat steps 6 thru 8.

Normally, lime removal will be completed within one hour.  Severe 

build-up of lime may take longer than an hour to complete descaling.

note:

 To check uN•lIMe for continued use, place some scale 

or white chalk in a glass with a small amount of uN•lIMe.  If 

the material is vigorously dissolved by the uN•lIMe, it can be 

reused; if not, the uN•lIMe should be replaced.

figure 27.

9.  Install  the  long  plastic  male  adapter  insert  fitting  into  the 

drain valve opening of heater after applying Teflon tape or 

paste to threads. Tighten firmly by hand and use wrench or 

adjustable pliers to check for secure connection. Do not over 

tighten to avoid damage to threads and fittings.

Prepare the up-N-Down Transfer Kit
The next step is the preparation on the up-N-Down Transfer Kit, 

if you have not already done so:
1.  With  the  5  gallon  up-N-Down  container  in  the  vertical 

position,  unscrew  the  plastic  vent  cap  in  the  handle  and 

pierce the plastic membrane over the vent boss under the 

cap to allow the container to vent.

note:

  If  your  container  does  not  have  the  vent  cap  and 

vent boss, drill a 3/16” hole in the handle.  When you have 

finished deliming you will be able to plug this drilled vent with 

the stainless steel screw that is supplied with the kit.

2.  remove the container’s cap and cut the plastic membrane 

located in the 3/4” IPT opening in the cap.  Take care to not 

damage the threads.

3.  Find the 3/4” male adapter, apply teflon tape to the threaded 

end and screw it into the 3/4” IPT opening in the cap.

4.  Put cap with male adapter back on the container and slide 

 

3/4” hose over end of male adapter and fasten in place using 

hose clamp provided.

Delime using Flo-Jug Method
5.  Slide the hose clamp over end of hose and slide hose over 

the  male  adapter  in  the  water  heater  drain  opening  and 

secure in place using hose clamp.

6.  lift container to the “Pour” Position, see Figure 27, being 

careful to keep the vent in the handle above the liquid level 

serViCe

system diagnostiCs

your  water  heater  is  equipped  with  an  ignition  control  that 

incorporates  a  diagnostic  system  to  assist  in  troubleshooting 

the  appliance. The  indicator  codes  on  the  ignition  module  are 

as follows:

taBle 9.

2 FlASHeS Flame sensed without call for heat
3 FlASHeS Ignition lockout

Steady On

Internal control failure

If  an  internal  control  failure  is  indicated,  replace  the  ignition 

control.
use  this  diagnostic  system  in  conjunction  with 

TrOubleSHOOTING” and the “SequeNCe OF OPerATION” 

to troubleshoot the appliance.

eleCtriCal serViCing

lAbel  All  WIreS  PrIOr  TO  DISCONNeCTION  WHeN 

SerVICING  CONTrOlS.  WIrING  errOrS  CAN  CAuSe 

IMPrOPer AND DANGerOuS OPerATION.
VerIFy PrOPer OPerATION AFTer  SerVICING.

Summary of Contents for SBL85 275NE

Page 1: ...ine or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any...

Page 2: ...ditions 32 Operational Conditions 32 Troubleshooting 33 Water Piping Diagrams 34 Notes 50 Limited Warranty 51 Table Of Contents Safe Installation Use and Service 3 APPROVALS 3 General Safety Informati...

Page 3: ...ate of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State...

Page 4: ...ation Contact a qualified installer or service agency for installation and service Excessive gas pressure to gas valve can cause serious injury or death Do not use water heater with any gas other than...

Page 5: ...ter system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow There should be no smoking or open flame near the faucet at...

Page 6: ...ting gas supply and electrical supply are required in addition to electrical testing skills when performing service ANSI Z223 1 2012 Sec 3 3 85 Qualified Agency Any individual firm corporation or comp...

Page 7: ...cause poor performance of the heater and can significantly reduce outlet water temperatures during heavy draws Note The Hydrocannon may have 1 3 or 7 cross tubes Figure 2 High Limit Switch The digital...

Page 8: ...Kg 900 lbs 408 Kg Table 2 Recovery Capacities based on 82 efficiency Input BTUH Input KW U S Gal Liters Eff U S Gallons Hr and Liters Hr at TEMPERATURE RISE INDICATED Deg F 36 40 50 54 60 70 72 80 90...

Page 9: ...maintained from serviceable parts The units are approved for installation with side rear and ceiling clearances as indicated below Table 4 Minimum Clearances to Combustible or non combustible construc...

Page 10: ...n labels from the manufacturer for placement on the blanket directly over the existing labels DO inspect the insulation blanket frequently to make certain it does not sag thereby obstructing combustio...

Page 11: ...MP WIRING DIAGRAM STORAGE TANK OR BUILDING RECIRCULATION FIELD SUPPLIED TEMPERATURE CONTROL INSTALLED IN THE STORAGE TANK OR CIRCULATING LOOP RETURN LINE CIRC PUMP MOTOR L1 HOT L2 NEUTRAL 120 VAC POWE...

Page 12: ...pressure and with all gas burning equipment running at maximum rate dynamic pressure The gas supply pressure must be stable within 1 5 W C 0 37 kPa from static to dynamic pressure to provide good perf...

Page 13: ...ge 20 and Water Piping Diagrams on page 34 Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized temper...

Page 14: ...not intended for the constant relief of thermal expansion A properly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Systems and Ther...

Page 15: ...tand instruction manual For safe operation an adequate supply of fresh uncontaminated air for combustion and ventilation must be provided An insufficient supply of air can cause recirculation of combu...

Page 16: ...Figure 15 Alternatively a single permanent opening commencing within 12 inches 300 mm of the top of the enclosure shall be provided See Figure 14 The water heater shall have clearances of at least 1 i...

Page 17: ...aggregate input rating of all appliances installed in the enclosure Each opening shall not be less than 100 square inches 645 cm2 Outdoor Air Through Two Vertical Ducts The illustrations shown in thi...

Page 18: ...HNICAL DATA VENTING MODEL SBL95 199NE Input 199 000 Btu hr Total Vent Height Feet Vent Connector Size 6 inches 6 8 10 15 20 30 50 100 Input Btuh hr Rise Vent Connector Diameter Inches 199 000 1 Ft 7 7...

Page 19: ...mon Vent Diameters Inches 2 550 000 10 9 9 8 8 8 7 7 3 825 000 12 12 12 10 9 9 8 8 4 1 100 000 14 14 14 12 12 10 9 9 MODEL SBL85 390NE A Input 390 000 Btu hr Total Vent Height Feet Vent Connector Size...

Page 20: ...installation of the water piping begins 1 Water Temperature Control and Mixing Valves on page 12 2 Dishwashing Machines on page 13 3 Temperature Pressure Relief Valve on page 13 4 Closed Systems and T...

Page 21: ...ing heat to this fitting Do not allow pipe dope to contact the plastic tube during installation Tube Inlet Installation Figure 19 TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES...

Page 22: ...tion AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION The controls of this water heater are polarity sensitive Be certain to properly wire the hot and neut...

Page 23: ...cordance with recommendations of serving gas suppliers Refer to the latest version of the National Fuel Gas Code To prevent damage care must be taken not to apply too much torque when attaching gas su...

Page 24: ...from faucets after extended periods of non use 1 Close the Main Gas Shutoff Valve see Figure 21 on page 23 2 Purge all air from the supply gas line up to the water heater s Main Gas Shutoff Valve 3 W...

Page 25: ...he supply gas regulator as necessary Adjust the supply gas regulator s per the regulator manufacturer s instructions to achieve the required static and dynamic supply gas pressure Multiple Appliance I...

Page 26: ...TO APPLIANCE and call your technician or gas supplier Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell gas...

Page 27: ...Valve Ignition Control maintains spark for up to 4 seconds and monitors Flame Sensor to determine if Burner is lit Does Burner light Ignition Control changes Blower from low speed to high speed after...

Page 28: ...y thermal expansion in a closed system See Closed Water Systems and Thermal Expansion on page 13 The Temperature Pressure Relief Valve is not intended for the constant relief of thermal expansion Temp...

Page 29: ...hismanual 11 Turn on the electrical supply to place the water heater back in operation 12 Turn on the gas supply to the water heater at the Main Gas Shutoff Valve 13 Allow the water heater to complete...

Page 30: ...pening and scrape out any loose deposits of scale or sediment This is an economical way to avoid unnecessary usage of the deliming solution Repeat the opening and closing of the cold water inlet valve...

Page 31: ...itting into the drain valve opening of heater after applying Teflon tape or paste to threads Tighten firmly by hand and use wrench or adjustable pliers to check for secure connection Do not over tight...

Page 32: ...be restarted unless the water temperature is reduced to approximately 120 F 49 C The high limit reset button on the front of the thermostat then needs to be depressed See Figure 2 for the location of...

Page 33: ...blockage and or flue gas exhaust blockage Water temperature too hot Thermostat set too high Set thermostat to a lower setting Rumbling Sediment accumulation on bottom of tank Drain a quantity of water...

Page 34: ...should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TE...

Page 35: ...ostat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP...

Page 36: ...and the storage tank s MULTI FLUE 1 UNIT WITH MIXING VALVE TWO TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BAL...

Page 37: ...mp between the water heater s and the storage tank s MULTI FLUE 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VA...

Page 38: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 39: ...tat should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 40: ...t should be set 5 degrees F higher than the Tank Temperature Control MULTI FLUE 2 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TAN...

Page 41: ...EMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SU...

Page 42: ...VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES C...

Page 43: ...LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING...

Page 44: ...an the Tank Temperature Control MULTI FLUE 3 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT B...

Page 45: ...than the Tank Temperature Control MULTI FLUE 3 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PO...

Page 46: ...RE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED...

Page 47: ...perature Control MULTI FLUE 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPE...

Page 48: ...emperature Control MULTI FLUE 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE T...

Page 49: ...49 Model Dimension A SBL95 199NE 76 SBL85 275NE A 76 SBL85 390NE A 76...

Page 50: ...50 Notes...

Page 51: ...an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an accepta...

Page 52: ...www statewaterheaters com 500 Tennessee Waltz Parkway Ashland City TN 37015 Tech Support 800 527 1953 Parts 800 433 2545 Copyright 2012 State Water Heaters All rights reserved...

Reviews: