Technical Primer - Aurora
4.5
Cement Foundation requirements for mounting the metal pedestal
4.5.1
Installation distance of parking space for column type single pile or double pile instal-
lation
When the Column-type Single pile or Double pile is installed in a single parking space or back-
to-back parking space, it is recommended that the linear distance between the vehicle block and the
Center of the charging pile is not less than 1200mm, as shown in Figure 8.
Figure 8: Installing at a parking place
4.5.2
Coulmn Installation steps
1. To start off with Column installation, use concrete base or metal base. The general assembly
scheme is shown in Figure 9a .
(a) Floor standing assembly drawing
(b) Inserting the cable into the column for installation
Figure 9: Installing the pedestal for Aurora
2. Lay the column horizontally and insert the wire from the bottom hole and exit from the middle
hole. (Figure 9b)
3. After connecting the inlet line with the pile body, fix the pile body on the vertical column. First,
use two cross M6*12 (Torque: 1.8 - 2.0 N.m) combination screws to fix the wall mount on the
column.
4. Hang the pile on the column, screw in two pattern M6*12 (Torque: 1.8 - 2.0 N.m) combination
screws at the bottom, as shown in Figure 10a.
5. Insert the hanger hook and guard cover into the mounting position and push them up, and
then lock them from the front with two M4*12 pattern composite screws (Torque: 1.4 - 1.6 N.m)
with column core head, as shown in Figure 10b.