Stahl SolConeX8581/31 Operating Instructions Manual Download Page 9

205582 / 8581615300
2014-10-10·BA00·III·en·03

Installation

9

SolConeX Switch Socket, 125 A 8581/
31

7.3 Opening / Closing the Enclosure

To open the enclosure

Loosen the cover screws.

Open the cover including the rotary handle. 

To close the enclosure

Close the cover including the rotary handle.

Tighten the cover screws to the specified torque (4.5 Nm).

7.4 Mounting and Operating Position

When mounting, make sure that

the hinged cover is at the bottom, the connection chamber is on top

the device is fixed in a vertical installation position to a plane wall using three screws 
(

d

 6 ... 8 mm) and suitable washers

all screws and nuts have been firmly tightened.

7.5 Electrical Connection

The information given in chapter "Technical Data" must be observed.

The conductor connection must be made with particular care.

The conductor insulation must reach up to the clamping points.

Do not damage the conductor (nicking) when removing the insulation.

Select suitable cables to be used and appropriate way of installing them to ensure that 
the maximum permitted conductor temperatures and the maximum permitted surface 
temperature are not exceeded.

 NOTICE

When explosion protected equipment is exposed to the weather, it is advis-
able to provide a protective cover or wall.

The elongated holes allow vertical and horizontal adjustment during mount-
ing.

 NOTICE

A protective conductor is always required.

Summary of Contents for SolConeX8581/31

Page 1: ...Operating instructions SolConeX Switch Socket 125 A 8581 31...

Page 2: ...2 Installation Conditions 9 7 3 Opening Closing the Enclosure 11 7 4 Mounting and Operating Position 11 7 5 Electrical Connection 11 7 6 Connection 12 8 Auxiliary Contacts 12 8 1 Mounting Auxiliary Co...

Page 3: ...installation place For correct operation please observe all other operating instructions enclosed in this delivery and the operating instructions of the equipment to be connected Safety Instructions N...

Page 4: ...lates fixed directly to the device 3 2 Modifications and alterations 3 3 Special Versions For special versions the actual components included in delivery may differ from the de scription given here in...

Page 5: ...auxiliary contacts for Ex i circuits E II 2 D Ex tD A21 ib IP66 T65 C Ta 30 40 C E II 2 D Ex tD A21 ib IP66 T75 C Ta 30 45 C Certificates IECEx IECEx PTB 06 0034 Europe ATEX PTB 01 ATEX 1161 Ambient...

Page 6: ...5 x 1 5 1 x M63 x 1 5 Enclosure material polyester glass fibre reinforced Degree of protection IP66 acc to IEC EN 60529 Auxiliary contacts Standard version 8080 1 1 1 NC contact 1 NO contact in left i...

Page 7: ...The devices must be stored in a dry place and vibration free 06556E00 06555E00 3 P PE 8581 31 4 3P N PE 8581 31 5 No of poles Frequency Rated operational voltage Colour code Earth contact sleeve posit...

Page 8: ...f electric shock Before opening the device disconnect it from the power supply WARNING Use approved components only For unused enclosure holes use R STAHL stopping plugs for unused cable entries use R...

Page 9: ...able washers all screws and nuts have been firmly tightened 7 5 Electrical Connection The information given in chapter Technical Data must be observed The conductor connection must be made with partic...

Page 10: ...d 1 NO contact in the left installation slot A maximum of 2 Type 8080 1 auxiliary contacts can be used The switching function of the auxiliary contact depends on the installation slot used see chapter...

Page 11: ...enclosed circuit diagram indicating the respective switching function to the rating plate of the switch 8 2 Dismounting Auxiliary Contacts Introduce the auxiliary contact key art no 201909 with the St...

Page 12: ...e that no components are damaged the device has been installed according to regulations there are no foreign bodies inside the device all screws and nuts have been firmly tightened the prescribed tigh...

Page 13: ...hort circuit in the Main Circuit 11 Cleaning The device may only be cleaned with a damp cloth 12 Disposal Observe the national waste disposal regulations NOTICE Switching on and off has to be done swi...

Page 14: ...iary contact series 8080 1 12446E00 2 NC contacts 8080 1 3 2 168356 0 026 1 NC contact 1 NO contact 8080 1 1 1 168351 0 026 2 NO contacts 8080 1 4 2 168353 0 026 The switching function of the auxiliar...

Reviews: