Technical data
6
205582 / 8581615300
2014-10-10·BA00·III·en·03
SolConeX Switch Socket, 125 A
8581/31
Switching capacity
acc. to IEC/EN 60947-3:
1)
1 contact
2)
2 contacts connected in series
3)
3 contacts connected in series
Short-circuit protection
Without thermal protection max. 125 A gG acc. to IEC/EN 60269-2
With thermal protection
max. 160 A gG acc. to IEC/EN 60269-2
Connection cross-section
Single conductor
connection
35 ... 150 mm
2
(AWG 2/0 ... 300 kcmil) stranded
50 ... 150 mm
2
(AWG 1/0 ... 300 kcmil) finely stranded
Multiple conductor
connection
2 x 35 mm
2
... 2 x 50 mm
2
(2 x AWG 2 ... 2 x AWG 1/0)
Only conductors of the same cross-section are permissible!
Connect PE terminal using cable lugs and assembly kit only (see "Accessories and Spare Parts"
Assembly kit Cable lugs, art. no. 211465)
Service life
electrical
20,000 operating cycles
Mechanical
100,000 operating cycles
Tightening torque
Main contacts
25 ... 30 Nm
Cover screws
4.5 Nm
Cable gland
1 x M63 x 1.5
(lateral positioning acc. to order possible)
Clamping range
31 ... 48 mm
Stopping plug
1 x M25 x 1.5, 1 x M63 x 1.5
Enclosure material
polyester, glass fibre reinforced
Degree of protection
IP66 acc. to IEC/EN 60529
Auxiliary contacts
Standard version
8080/1-1: 1 NC c 1 NO contact in left installation slot
NO contact ON delayed
NO contact OFF leading (> 20 ms before opening of the main contacts)
NC contacts synchronizing
Possible auxiliary contacts max. 2 auxiliary contact blocks of type 8080/1 (slow-action contacts)
8080/1-1: 1 NC contact / 1 NO contact
NO contact ON delayed
1)
NO contact OFF advanced (> 20 ms before opening of the main contacts)
1)
NC contact synchronising
8080/1-3: 2 NC contacts
2)
8080/1-4: 2 NO contacts
2)
1)
only in the left installation slot, synchronising in the right installation slot
2)
synchronising in all installation slots
Rated operational voltage
250 V AC / DC
400 V AC, for equal potential of both contacts
500 V AC, when 1 NC + 1 NO and the same potential of both contacts is used
Rated operational current
max. 6 A
Short-circuit protection
10 A, tripping characteristic gG acc. to IEC/EN 60269-1
Connection cross-section
1.5 ... 2.5 mm
2
(AWG 16 ... 14) solid / finely stranded
Tightening torque
0.4 Nm
AC-3
DC-23
DC-1
690 V, 125 A
220 V, 125 A
3)
220 V, 125 A
3)
120 V, 125 A
2)
120 V, 125 A
2)
60 V, 125 A
1)
60 V, 125 A
1)