Mounting and Installation
30
147924 / 8146647300
2018-12-06·BA00·III·en·12
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Safety switch / load disconnect switch
Series 8146/5-V37, Series 8150/5-V37,
Series 8146/5-V11
7.1.2 Busbar Terminal for Round Conductors 50 to 240 mm
2
7.1.3 PE/PA/N Rails
Rail size 1 (10 mm x 3 mm) max. 80 A
Rail size 2 (12 mm x 4 mm) max. 110 A
Rail size 3 (18 mm x 6 mm) max. 250 A
clampable conductor cross-sections:
finely stranded
50 to 185 mm
2
stranded
50 to 240 mm
2
Tightening torque
15 Nm
Dimensional drawings (all dimensions in mm) – Subject to modifications
16138E00
Connection
cross-
section
1 x 0.75 to 4 mm
2
with core end sleeve
2 x 0.75 to 4 mm
2
conductors with the same cross-section and structure
1 or 2 ring cable lugs M4
With lug: 1 x 6 to 10 mm
2
Torque: 1.2 Nm
Connection
cross-
section
1 x 1.5 to 10 mm
2
with core end sleeve
2 x 1.5 to 10 mm
2
conductors with the same cross-section and structure
1 or 2 ring cable lugs M5
With lug: 1 x 16 to 35 mm
2
Torque: 2 Nm
Connection
cross-
section
Lug M6 (5 Nm): 1 x 1.5 to 10 mm
2
Lug M8 (10 Nm): 1 x 16 to 70 mm
2
Summary of Contents for Reihe 8146/5-V11