10.2.2 

Tightening torque 

10.2.2.1 

Terminals 

 

The stipulated tightening torques of the connection terminals must be 
observed  and  applied.  Again,  they  must  be  checked  and  possibly 
adjusted before commissioning ! 

 

10.2.2.2 

Cable glands 

The tightening torques for the cable glands may vary depending on the cables and wires used. 
The  users  have  to  determine  and  apply  the  required  torques  themselves.  In  the  case  of  ex-
factory  systems,  all  components  are  installed  correctly  and  in  accordance  with  applicable 
standards.  Since  storage  or  temperature  etc.  can  have  an  impact  on  the  cables  and  cable 
glands,  the  pre-installed  screw  connections  must  be  checked  and  possibly  tightened  before 
commissioning. 
If  they  are  too  loose  or  too  tight,  the  type  of  protection,  sealing  or  strain  relief  might  be 
negatively impacted. 
Cable glands with cap nut and without strain relief clamp should only be used for permanently 
installed cables and electrical lines. Installation of the required strain relief is the responsibility of 
the system set-up engineer. 
 

10.3  Safety information for operation 

  Operate  the  device  only  if  it  is  clean  and  undamaged.  If  the  device  is  in  any  way 

damaged, do not touch it to avoid injury. In the case of any damage that may compromise 
ingress protection (e.g. cracks, holes or broken components) the device must be taken out 
of  commission  immediately.  Before  the  device  is  recommissioned  the  damaged 
components must be replaced. 

  If you want to use the device in zone 20, 21 or 22 as EPL Da/Db/Dc, dust deposita of a 

thickness exceeding 5 mm must be removed and you have to ensure that no high-energy 
loading mechanisms at the operating surface of the unit (e.g. pneumatic particle transport) 
occur during operation. The device may not be used in environments where propagating 
brush discharges may occur. 

  In  general,  and  particularly  when  opening  and  closing  enclosures,  users  must  take  care 

not to get injured by getting caught / trapped. 

  In case of non-compliance or contravention of the above explosion-protection is no longer 

guaranteed and all warranty claims shall be null and void. 

 

10.4  Special conditions 

Equipotential  bonding  must  be  established  for  the  external  intrinsically  safe  circuits  of  the 
accessories to be connected, e.g. display, keyboard or pointer device. 
 

 

 

NOTICE

 

Summary of Contents for MT 7 Series

Page 1: ...S 600 KVM Systems R STAHL HMI Systems GmbH Adolf Grimme Allee 8 D 50829 K ln HW Rev MT 4x7 01 01 00 HW Rev MT 5x7 01 01 00 HW Rev MT 6x7 01 01 00 HW Rev MT 4x7 BT 01 01 03 HW Rev MT 5x7 BT 01 01 03 HW...

Page 2: ...ical changes without notice Any warranty claims are limited to the right to demand amendments Liability for any damage that might result from the contents of these instructions or all other documentat...

Page 3: ...ormation of which particular note should be taken Information highlighted by this symbol refers to a different chapter or section in this manual or other documentation or a web page Warnings Caution I...

Page 4: ...3 11 3 2 Additionally for MT 5x7 Thin Clients 11 3 2 1 All devices up to hardware revision 01 01 00 11 3 2 2 All devices starting from hardware revision 01 01 01 11 3 2 3 All devices starting from har...

Page 5: ...9 12 1 General information 29 12 2 Connections 29 13 General Information 32 13 1 Touch driver 32 13 2 MT 4x7 Panel PC and MT 5x7 Thin Client 32 13 2 1 Up to Windows 7 operating systems 32 13 2 1 1 Lic...

Page 6: ...es 2 and 22 with interfaces for zones 0 1 2 and 20 21 22 The devices are connected to a communication system via the serial interfaces RS 232 Ethernet located in their connection box at the rear The c...

Page 7: ...of the 500 SERIES can be integrated into modern networks as Thin Clients or with a KVM box via KVM over IP Digital Ethernet technology is used for the data transfer between KVM box and Remote System U...

Page 8: ...scratched with high pressure force the spacer dots could be damaged Glass touch Quite good but with high pressure force the spacer dots could be damaged Touchscreen scratch hardness MoHS Foil touch G...

Page 9: ...ium battery and capacitor buffered maintenance free Battery 5 years Capacitor at least 4 days Cable type optical fibre SX LX MM SM Multi mode optical fibre cable 50 m core cross section and 125 m exte...

Page 10: ...eration 5 C 40 C 41 F 104 F Storage temperature range 20 C 70 C 4 F 158 F Heat dissipation about 40 via the front plate and 60 via the enclosure Relative humidity 10 to 90 at 40 C 104 F non condensing...

Page 11: ...7 Thin Clients 3 2 1 All devices up to hardware revision 01 01 00 Processor AMD Geode LX 800 266 MHz RAM 512 MB 2 GB Data memory 1 GB 16 GB Operating system Windows Embedded Standard 2009 and Remote F...

Page 12: ...3 Function Equipment MT 667 MT 677 MT 687 Resolution in pixels 1680 x 1050 1920 x 1080 1920 x 1200 1280 x 1024 1600 x 1200 1920 x 1080 1280 x 960 1600 x 1000 1680 x 1050 1152 x 864 1400 x 1050 1600 x...

Page 13: ...etic compatibility EMV directive 2014 30 EU Classification EN 61000 6 2 2006 Interference resistance EN 61000 6 4 2007 A1 2011 Interference emission Low voltage directive Directive 2014 35 EU EN 60950...

Page 14: ...ervision and Test Centre for Explosion Protected Electrical Products Marine certification DNV GL Det Norske Veritas Germanischer Lloyd 5 1 ATEX The ATEX certificates are listed under the following cer...

Page 15: ...ted under the following certificate number Certificate number TAA00000BK 6 Marking Manufacturer R STAHL HMI Systems GmbH Type code MT 4x7 MT 5x7 MT 6x7 CE classification c 0158 Testing authority and c...

Page 16: ...pending on type Power consumption Imax 5 A Power Pmax 150 W Max operating voltage Um 250 VAC Short circuit current IK 1500 A USB X13 Rated voltage 5 VDC 10 Max operating voltage Um 250 VAC 12 V X14 Ra...

Page 17: ...intrinsically safe circuits Keyboard X11 The maximum values are Ui 5 5 C Uo 5 5 C Ii 3 A lo 309 mA Pi 2 W Po 629 mW Ci negligible F Co 50 F Li negligible mH Lo 40 H Pointer device X12 The maximum val...

Page 18: ...Ethernet interface 10 100Base TX Ex nA MT 4x7 aa TFT cc dd ee ff gg hh TFT display standard MT 4x7 aa bb T dd ee ff gg hh Touch screen membrane MT 4x7 aa bb TG dd ee ff gg hh Touch screen glass MT 4x...

Page 19: ...er Ethernet interface 1000Base LX Ex op is single mode MT 4x7 TX BT bb cc dd ee ff gg hh ii Copper Ethernet interface 10 100Base TX Ex nA MT 4x7 2TX BT bb cc dd ee ff gg hh ii 2x Copper Ethernet inter...

Page 20: ...ct type Product key structure Description Type with MT 5x7 SX bb cc dd ee ff Optical fibre Ethernet interface 1000Base SX Ex op is multi mode MT 5x7 TX bb cc dd ee ff Copper Ethernet interface 10 100B...

Page 21: ...l fiber Ethernet interface 1000Base LX Ex op is single mode MT 5x7 TX BT bb cc dd ee ff gg hh ii Copper Ethernet interface 10 100Base TX Ex nA MT 5x7 2TX BT bb cc dd ee ff gg hh ii 2x Copper Ethernet...

Page 22: ...c dd ee ff gg hh ii 2x Copper Ethernet interface 10 100Base TX Ex nA MT 577 SX P2 bb cc dd ee ff gg hh ii Optical fiber Ethernet interface 1000Base SX Ex op is multi mode additional 1x copper Ethernet...

Page 23: ...2 KVM with direct copper connection Gigabit Ex nA MT 6x7 DVI3 CAT bb cc dd ee ff gg DVI3 KVM with direct copper connection Gigabit Ex nA MT 6x7 DVI3 MM FO bb cc dd ee ff gg DVI3 KVM with direct optica...

Page 24: ...esign a small gap between the touch surface and the cover Therefore the devices should not be used in high pollution environments Under conditions of high pollution the manufacturers understand areas...

Page 25: ...aired in hazardous atmospheres sole exception the connection box All circuits must be completely de energised before the device is connected Before opening the connection box ensure that all circuits...

Page 26: ...intrinsically safe device After the device has been operated as intrinsically safe with a low level of protection e g an Ex ia device at an Ex ib interface it may no longer be operated in applications...

Page 27: ...relief is the responsibility of the system set up engineer 10 3 Safety information for operation Operate the device only if it is clean and undamaged If the device is in any way damaged do not touch...

Page 28: ...s Additional specific safety regulations apply to electronic and pneumatic installations 11 2 Cut out MT xx7 Make a cut out with the following dimensions Width Height Depth of cut out Material thickne...

Page 29: ...VAC Power supply PWR 2 Power supply HMI device 0 VDC or 100 240 VAC of the HMI device 3 Earth connection Ex nA X11 1 UB Red USB interface KBi 2 D White Ex ia 3 D Green for 4 GND Black External keyboa...

Page 30: ...l SER 2 RxD Blue Ex nA interface 3 RTS White Orange RS 232 4 CTS Orange 5 GND Black X101 1 Signal FBAS White Video CAM 2 Screen GND Black Ex nA interface optional not for MT 577 P2 devices X105 1 CH1...

Page 31: ...econd Ethernet TX copper interface in the TX version 1TX not available If display types MT xx7 DVI1 MM or MT xx7 DVI1 SM optical fibre versions are used terminal X16 remains unused In the case of an o...

Page 32: ...perating systems When using the Windows Embedded operating systems XP or Windows Standard 2009 7 on the Panel PC devices SERIES 400 the C system drive can be protected from unauthorised writing EWF Th...

Page 33: ...ase contact our Support department 13 2 3 Initial start up MT 4x7 Panel PC When the device is started for the first time the Windows installation assistant starts where users have to select certain se...

Page 34: ...properly see illustration below and NOT simply switched off Otherwise the existing image of the device may be damaged rendering the HMI device non functioning 13 2 7 Data loss In the case of applicat...

Page 35: ...ick the No hazloc approved panel mount option on the device The device is only approved for installation inside an Ex e or Ex tb enclosure if no No hazloc approved panel mount option is indicated on t...

Page 36: ...he table below old new Directive WEEE I Directive 2002 96 EC WEEE II Directive 2012 19 EU Valid until 14 08 2018 from 15 08 2018 Category 9 Monitoring and control devices SG2 Screens monitors and equi...

Page 37: ...ng Instructions MT xx7 Mounting inside enclosure with MT xx7 mounting set R STAHL HMI Systems GmbH OI_MT_xx7_en_V_01_02_14 docx 06 12 2019 Page 37 of 44 17 Mounting inside enclosure with MT xx7 mounti...

Page 38: ...Operating Instructions MT xx7 Mounting inside enclosure with MT xx7 mounting set Page 38 of 44 R STAHL HMI Systems GmbH OI_MT_xx7_en_V_01_02_14 docx 06 12 2019...

Page 39: ...Operating Instructions MT xx7 Declaration of EC conformity R STAHL HMI Systems GmbH OI_MT_xx7_en_V_01_02_14 docx 06 12 2019 Page 39 of 44 18 Declaration of EC conformity...

Page 40: ...Operating Instructions MT xx7 Declaration of EC conformity Page 40 of 44 R STAHL HMI Systems GmbH OI_MT_xx7_en_V_01_02_14 docx 06 12 2019 18 1 RCM...

Page 41: ...Operating Instructions MT xx7 Declaration of EC conformity R STAHL HMI Systems GmbH OI_MT_xx7_en_V_01_02_14 docx 06 12 2019 Page 41 of 44...

Page 42: ...ap between touch surface and cover Addition of section Connections with TX interface for MT 577 2TX P2 device only Addition of section Connections FO interface not for MT 577 2TX P2 device Addition of...

Page 43: ......

Page 44: ...stems GmbH Adolf Grimme Allee 8 D 50829 K ln T switchboard 49 221 76 806 1000 Hotline 49 221 76 806 5000 F 49 221 76 806 4100 E switchboard office stahl hmi de hotline support stahl hmi de r stahl com...

Reviews: