Operating Instructions MT-xx7
Power supply
Page 16 of 44
R. STAHL HMI Systems GmbH / OI_MT_xx7_en_V_01_02_14.docx / 06.12.2019
7
Power supply
7.1
HMI devices
Power supply:
24 VDC or 100
– 240 VAC, 50 – 60 Hz
Power consumption:
at 24 VDC
max. 3 A
at 100 - 240 VAC
max. 1 A
8
Permitted maximum values
8.1 External, non-intrinsically safe circuits
Input voltage "PWR" (X10):
Nominal voltage:
20 ...240 VAC/VDC (depending on type)
Power consumption I
max
≤ 5 A
Power P
max
≤ 150 W
Max. operating voltage U
m
≤ 250 VAC
Short-circuit current I
K
≤ 1500 A
USB (X13):
Rated voltage
5 VDC (±10 %)
Max. operating voltage U
m
≤ 250 VAC
12 V (X14):
Rated voltage
12 VDC (±10 %)
Power consumption Imax
≤ 400 mA
Max. operating voltage U
m
≤ 250 VAC
RS-232 "SER" (X97):
Rated voltage
15 VDC (±10 %)
Max. operating voltage U
m
≤ 250 VAC
Video "CAM" (X101):
Rated voltage
5 VDC (±10 %)
Max. operating voltage U
m
≤ 250 VAC
Audio "AUD" (X105):
Rated voltage
100 VDC (±10%)
Max. operating voltage U
m
≤ 250 VAC
Copper Ethernet (CAT7 1) (X16):
Rated voltage
5 VDC (±10 %)
Max. operating voltage U
m
≤ 250 VAC
Summary of Contents for MT 7 Series