Operating instructions 

Additional languages www.r-stahl.com  

EN

Emergency Luminaire with LED

Series EXLUX 6009/4

Summary of Contents for EXLUX 6009/4 Series

Page 1: ...EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Operating instructions Additional languages www r stahl com EN Emergency Luminaire with LED Series EXLUX 6009 4...

Page 2: ...d Use 6 3 4 Modifications and alterations 6 4 Function and device design 6 4 1 Function 6 4 2 Device design 7 5 Technical data 9 6 Engineering 13 6 1 Mains operation 13 6 2 Emergency light blocking 14...

Page 3: ...eclaration of Conformity www r stahl com The device has IECEx approval For certificate please refer to the IECEx homepage http iecex iec ch Further national certificates can be downloaded via the foll...

Page 4: ...Type and source of danger damage Consequences of danger Taking countermeasures to avoid the danger or damage Symbol Meaning Tips and recommendations on the use of the device Danger due to explosive a...

Page 5: ...y the technical data We cannot be held liable for damage to the device caused by incorrect or unauthorised use or non compliance with these operating instructions For assembly and installation Observe...

Page 6: ...re is approved for use in hazardous areas of Zones 1 21 2 and 22 Mode of operation A weekly functional test has been permanently integrated An annual rated operating time test can be deactivated and a...

Page 7: ...EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Emergency Luminaire with LED Series EXLUX 6009 4 4 2 Device design 20300E00 1 I S Module 5 Cable entry 2 Control gear 6 Connection te...

Page 8: ...300190 2018 11 09 BA00 III en 00 EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Emergency Luminaire with LED Series EXLUX 6009 4 20301E00 9 LED indicator 11 LED PCB 10 Moun...

Page 9: ...Certifications and certificates Certificates IECEx ATEX Technical Data Electrical data Rated operational voltage AC 110 to 230 V 10 50 to 60 Hz Rated operational current Power factor Rated insulation...

Page 10: ...IK10 IEC 62262 Luminous characteristics Colour rendering Ra 80 Colour temperature 4 000 K 5 000 K or 6 500 K depending on the variant Luminous flux Values apply to Ta 25 C Luminous flux decrease at a...

Page 11: ...n glass fibre reinforced Colour Grey colour similar to RAL 7035 Seal Silicone seal foamed into the translucent cover Translucent cover Polycarbonate Luminaire locking Central lock for M8 A F 13 box sp...

Page 12: ...s disconnected by means of a switch The battery set can be replaced after disconnecting the plug in contacts Technical Data Standard luminaire with Luminaries are equipped with internal through wiring...

Page 13: ...e light fitting is switched off 6 1 2 Continuous operation The light fitting is switched on Optional DALI connection DALI interface in accordance with IEC 62386 202 2009 08 and IEC 62386 207 2009 08 B...

Page 14: ...ng 6 2 Emergency light blocking A remote switch for emergency light blocking can be connected to terminals 10 and 12 of the control gear 16399E00 18475E00 Remote switch is closed Remote switch is open...

Page 15: ...The remote switch is directly connected to the control gear The following connection versions are possible Point to point connection Linear connection The following conductor specifications must be o...

Page 16: ...of deep battery discharge due to exceeded storage Non compliance can result in material damage The battery should be charged within 26 weeks from date of production by means of operating the luminair...

Page 17: ...drawings for assembly parts and accessories all dimensions in mm inches Subject to alterations 15778E00 15779E00 Mounting rail M25 x 1 5 183 5 7 22 125 L3 L2 L1 L3 L2 4 92 M25 x 1 5 Dimen sions Lumin...

Page 18: ...ing bracket fitted in mounting rail Pipe clamp fitted in mounting rail 15780E00 03257E00 Wall mounting bracket fitted in mounting rail Bracket for wall mounting with pipe section 17755E00 Dimensions L...

Page 19: ...avoided accidental friction particle currents DANGER Explosion hazard due to inadmissible heating Non compliance results in severe or fatal injuries Avoid external heat sources and or direct sunlight...

Page 20: ...mounting sleeve 16325E00 16326E00 Mounting bracket Top rail Lateral mounting pockets for variable points of suspension When mounting the luminaire using top rails ensure that the mounting surface is...

Page 21: ...ion Pole mounting using pipe clamps 16327E00 16328E00 Size L4 mm inch L mm inch 2 320 12 60 80 3 15 4 670 26 38 130 5 12 For pipe clamp mounting use the solution of R STAHL Schaltger te GmbH with inte...

Page 22: ...Opening and Closing of the Enclosure 15515E00 15517E00 Size L4 mm inch L mm inch 2 320 12 60 80 3 15 4 670 26 38 130 5 12 DANGER Risk of electric shock due to improper opening Non compliance results i...

Page 23: ...tral lock opening protection against dirt Observe the following during mounting and dismounting Version without switch Disconnect the luminaire from the power supply secure it against being switched o...

Page 24: ...onnecting to the main supply Clamping must be carried out precisely Do not clamp any part of the conductor insulation Do not interchange the conductors Observe the technical regulations when connectin...

Page 25: ...lamping range 1 x 1 5 to 6 mm2 solid finely stranded 2 free clamping units per pole available Stripping length 10 to 12 mm Standard 20294E00 with DALI connection 20302E00 Through wiring with 2 5 mm2 c...

Page 26: ...tightened using the following values Luminaires with approved cable entries and stopping plugs not supplied by R STAHL Schaltger te GmbH 18475E00 Clamping range 1 5 mm2 solid finely and extra finely s...

Page 27: ...en inserted correctly Check if all screws and nuts have been tightened firmly Check if all drilled holes are closed Check whether all the cable entries and stopping plugs have been tightened firmly Ch...

Page 28: ...rgency light operation The luminaire is switched on regardless of the operation mode of the selected rated operating time Rated operating time Stand by operation The luminaire is switched off regardle...

Page 29: ...s shown on the LED indicator During a test the luminaire is switched on Function test starts within 24 hours after commissioning is carried out every 7 days takes 1 minute checks the function of the L...

Page 30: ...Function test green LED 2 to 4 Function test red LED 4 to 10 Status rated operating time test Green LED flashes rated operating time test active Green LED off rated operating time test not active Gree...

Page 31: ...ber of the device Purchase information Error description Intended use in particular input output wiring Cause of error Troubleshooting The LEDs are defective Replace the mounting plate including LEDs...

Page 32: ...signs of ageing or damage completely replace enclosure components with damaged foamed seal Whether the device is clean inside and out Whether the permissible temperatures in accordance with EN 60079 a...

Page 33: ...Lift the translucent cover to detach it from the hinge Insert new translucent cover into the hinge All hinges must engage correctly Close the luminaire Observe safety notes DANGER Explosion hazard du...

Page 34: ...N EN Emergency Luminaire with LED Series EXLUX 6009 4 Loosen the screws 1 cross head H2 in the battery cover 2 Open the battery case The switch 6 disconnects the battery circuit Secure the battery cov...

Page 35: ...et jammed Tighten the screws 1 cross head H2 firmly 2 Nm Resetting the error indication blinking red after replacing the battery 16406E00 The error indication blinking red remains active after success...

Page 36: ...tion will be sent R STAHL s customer service will contact you You will receive an RMA slip after speaking with customer service Send the device along with the RMA slip in the packaging to R STAHL Scha...

Page 37: ...due to chemical reactions Human health and the environment are at risk Batteries collect them separately dispose of them in controlled fashion do not dispose of them in the domestic waste return them...

Page 38: ...arking marquage r v II2 G Ex db eb ib mb op is IIC T4 Gb r r W II2 D Ex tb op is INC T 100 C Db V S 0158 EU Baumusterpr fbescheinigung EU Type Examination Certificate Attestation d examen UE de type I...