154099 / 8591601300
S-BA-8591-04-en-04/09/2009
General Safety Information
5
Ex Plug Connector miniClix
8591/1, 8591/4
X
Installation permitted in walls of enclosures designed with type of protection Increased
Safety "e".
X
Plastic versions of the plug connector must be mechanically protected at temperatures
below -20°C.
X
Do not use angled adaptors made of plastic with temperatures below -20°C.
If using terminal compartments of type of protection Increased Safety "e"
according to IEC/EN 60079-7:
X
Observe the clearance and creepage distances.
Equipotential bonding
X
Ensure equipotential bonding or earthing by attaching metal versions of the flange
sokket, device plug and/or angled adaptor to the entire plant.
3.4 Conformity to Standards
The plug connectors have been developed, manufactured and tested according to the
state-of-art and EN 29001 (ISO 9001).
Among others, they comply with the following regulations and standards:
X
94/9/EG
X
IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 60079-11,
IEC/EN 60079-14
X
IEC/EN 61241-0, IEC/EN 61241-1
Summary of Contents for Ex Plug Connector miniClix