221787 / 9160617310
2015-10-05·BA00·III·en·03
Mounting and installation
15
Transmitter Supply Unit Ex i
Series 9160
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
8.3.2 Schematic diagram
See device labelling.
For the connection cross-sections of the wiring to be connected, refer to the data sheet.
Input wiring (blue terminals with pins 10, 11, 12 and 13, 14, 15):
Output wiring (black terminals with pins 1, 2, 3 and 4, 5, 6):
8.3.3 Connection of supply
2-wire
transmitter
3-wire
transmitter
mA-Source
4-wire
transmitter
Channel 2
06980E00
06979E00
06981E00
Channel 1
06976E00
06977E00
06978E00
9160/..-11-1.
9160/..-10-10
9160/19-10-..
9160/19-11-1.
Channel 2
09742E00
09741E00
04813E00
15706E00
Channel 1
09744E00
09743E00
09743E00
09744E00
For a functioning HART communication in the output circuit a load resistance
of at least 250 Ω is necessary (e.g. input resistance of the input sub-assem
-
bly). If not available, the internal 221 Ω resistor can be used additionally.
In this case, the connection must be made to the terminals "3+/2-" or "4+/6-".
The maximum output load is reduced to 479 Ω. For variants 9160/19-11-11
and 9160/19-10-10 a HART communication is supported on channel 1 only.
Type of supply
Connection
Direct supply of the device via 24 V connec
-
tion
Green terminals "7+" and "9-"
Supply via pac-Bus
pac-Bus terminals "1+" and "2-"
13+
14
+
0/4 ... 20 mA
13+
14
15-
14+
15-
+
-
10
12+
+
0/4 ... 20 mA
10
11-
12+
10+
11-
+
-
4/5+
6-
RL
4/5+
6-
RL
4/5+
6-
RL
4/5+
6-
RL
3 1
/ +
2-
RL
3/1+
2-
RL
3/1+
2-
RL
3 1
/ +
2-
RL