background image

Operation, Installation and Maintenance Manual for 6414/11-Series 

 

 

ID-No.:  

                   240912 / 6414603300

 

Publication Code:          2015-04-30:BA00.lll.en.00                                                                                                                                                                                Page - 12 - of 17 

 

 

Note: 

a)

 

 Version without switch: Disconnect the luminaire from the power supply and secure it against being switched on again. 

b)

 

 Version with switch: The luminaire is positively disconnected from the power supply by actuating the central lock. 

c)

 

 In opened condition and with luminaire cover swiveled down, a restart lock-out device prevents the central lock from being 

actuated. 

d)

 

 Please do not use force! 

e)

 

 Only when the luminaire cover is closed, the central lock can be engaged. 

f)

 

While trying to open or close, keep the Allen key pressed to the lock and then turn. 

 

Opening and closing the reflector plate 

 

1

 

Open the reflector plate by two(2 No’s) quarter turn screws. 

2

 

Swivel down the reflector plate as shown in the diagram below. 

3

 

When closing, flip up the reflector plate, snap it into place and fix it with by two(2 No’s) quarter turn screws.

 

 

                   

 

                           

 

 

 

 

 

 

quarter turn screws

 to Lock the reflector Plate – 2 No.’s  

 

 

7.3.2 

Electrical Connections: 

 
Observe the maximum clamping possibility of the connecting terminals (see chapter "Technical data"). 

For optional screw-type terminals, two conductors per clamping unit can be clamped (incoming and outgoing wiring). 

 

Note: 

 

Clamping must be carried out precisely! 

 

Do not clamp any part of the conductor insulation! 

 

Do not interchange the conductors! 

 

Observe the technical regulations when connecting the conductor! 

 

Clamp the conductor firmly. 

 

Optional screw-type terminals: Firmly tighten screws (tightening torque 2 Nm, for unused clamping units 0.7 Nm)! 

 

The terminal cover of optional screw-type terminals does not have to be removed to clamp the conductor! 

Summary of Contents for 6414/11 Series

Page 1: ...Manual for 6414 11 Series ID No 240912 6414603300 Publication Code 2015 04 30 BA00 lll en 00 Page 1 of 17 Operating instructions For Additional languages www stahl ex com Linear Luminaire Sheet Steel...

Page 2: ...3 2 Safe Use 4 3 3 Intended Use 5 3 4 Modification and Alterations 5 4 Function and Device Design 5 4 1 Function 6 4 2 Device design 6 5 Technical Data 7 6 Transport and Storage 8 7 Mounting Installa...

Page 3: ...ons ID No 240912 6414603300 Publication Code 2015 04 30 BA00 lll en 00 The original instructions are the English edition They are legally binding in all legal affairs 1 3 Conformity to Standards See c...

Page 4: ...s Non compliance with the instruction can result in minor or light injuries to persons NOTICE Avoiding material damage Non compliance with the instruction can result in material damage to the device a...

Page 5: ...s prohibited Installation maintenance overhaul and repair may only be carried out by appropriately authorized and trained personnel Non compliance to this could be fatal or could result in damage to t...

Page 6: ...lighting areas work spaces and objects switching off the equipment by means of a central lock Optional version when the luminaire is opened For lighting areas work spaces and objects Pharma Chemical...

Page 7: ...50 60 Hz Lamp operation DC 2 lamp Lamp standard IEC 60081 Lamp power 18 36 58 W Nominal current 2x 18 W 150 mA 4x 18 W 300 mA 2x 36 W 300 mA 4x 36 W 600 mA 2x 58 W 480 mA 4x 58 W 960 mA Lamp Wattage 1...

Page 8: ...Optional With Disconnect Switch Light technical data Lamps Two pin fluorescent lamps 26 mm diameter for holder G13 2 x 18 W 4 x 18 W 2 x 36 W 4 x 36 W 2 x 58 W 4 x 58 W Installation notes Looping thr...

Page 9: ...ublication Code 2015 04 30 BA00 lll en 00 Page 9 of 17 7 1 Dimensions fastening dimensions Dimensional Drawings All Dimensions in mm inch Subject to Alterations Model 2x18W 4x18W 2x36W 4x36W 2x58W 4x5...

Page 10: ...on protection is impaired Do not install within arm s reach Ensure that no electrostatic charging may occur For example due to accidental friction with particle streams by cleaning with a dry cloth Th...

Page 11: ...ire by using a socket wrench from R STAHL Schaltger te GmbH 1 Remove the closing cap of the central lock 2 To open the fixture press inward and Turn the central lock using a socket key M5 hex socket h...

Page 12: ...reflector plate by two 2 No s quarter turn screws 2 Swivel down the reflector plate as shown in the diagram below 3 When closing flip up the reflector plate snap it into place and fix it with by two...

Page 13: ...mm 10 11 mm Through wiring NOTE Through wiring with 2 5 mm 2 cross section for max 12 A 7 3 3 Cable Entries The standard luminaire is delivered with 3 lead in holes 1 cable gland and 2 stopping plugs...

Page 14: ...device before commissioning Explosion protection is impaired Comply with the National regulations Check the device for proper installation and function before commissioning Before commissioning ensur...

Page 15: ...on ready Type and serial number Purchase information Error description Intended use in particular input output wiring 10 Maintenance and repair WARNING Unauthorized work being performed on the device...

Page 16: ...ely change enclosure components with foamed seal if the conductors are clamped properly clamp loose conductors tightly 10 1 1 Replacement of lamps Only use fluorescent lamps with pins made of brass In...

Page 17: ...als when sending it for recycling Ensure environmentally friendly disposal of all components according to the statutory regulations 12 Accessories and Spare Parts NOTE Use only original accessories an...

Reviews: