7.3
Installation
7.3.1
Opening and Closing of the Enclosure
DANGER
Risk of electric shock!
Risk of fatal injuries!
Luminaires without switch must not be opened when they are supplied with power (see
information plate on the lock)!
Recommendation
Opening and closing of the luminaire by using a socket wrench from R. STAHL
Schaltgeräte GmbH.
1.
Remove the closing cap of the central lock.
2.
To open the fixture, press inward and Turn the central lock using a socket key M5 hex socket head driver, by 90° anti-clockwise direction
as far as it can go. Before turning, make sure to press the lock as shown in the picture below.
3.
Swivel down the lighting trough (Support the Glass while performing step no. 2 of this section).
4.
Proceed in reverse order to close.
5.
The seal of the luminaire trough must lie correctly on the sealing edge.
6.
Push the closing cap onto the central lock opening (To avoid dust accumulation).