Explosion Protection
Global (IECEx)
Gas and dust
IECEx PTB 13.0049
Ex nR op is IIC T6 Gc or Ex nRc op is IIC T6
Ex tc IIIC T80 °C Dc or Ex tc IIIC T80 °C
Europe (ATEX)
Gas and dust
PTB 13 ATEX 2020
E
II 3 G Ex nR op is IIC T6 Gc or Ex nRc op is IIC T6
E
II 3 D Ex tc IIIC T80 °C Dc or Ex tc IIIC T80 °C
Certifications and certificates
Certificates
IECEx, ATEX
Technical Data
Electrical data
Ballast
AC: 220 V ... 240 V ± 10 %; 50 ... 60 Hz
DC: 196 V ... 240 V ± 10 %
Inrush current
I
peak
= 53 A; Δt = 200
m
s
max. light fittings per circuit breaker:
Power factor
)
0.93
Disconnection of the
light
When opening the luminaire
Switch with safety lock (optional); when opening the central lock all poles of the
voltage supply to the ballast are disconnected; contacts of the switching
element are positive opening, they can only be switched on again when the
luminaire trough and the central locking system are closed.
Luminous characteristics
Colour temperature
5700 K
Colour rendering
Ra
)
70
Typ
10 A
16 A
20 A
25 A
B
8
13
16
20
C
13
22
27
34