221664 / YL6S60300010
2022-03-14·BA00·III·en·05
Technical data
9
DE
EN
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
KR
CN
GRP combination signal – 110 db(A)/
5 joules, flameproof
Series YL6S
Technical data
Electrical data
Rated operational
voltage
24 or 48 V DC
115 or 230 V AC
Start-up current
24 V / 48 V DC
115 V AC
230 V AC
I
max
Duration
I
max
Duration
I
max
Duration
17.7 A
220 μs
21 A
500 μs
33 A
310 μs
Calculated values. Combination signal consists of two separate electrical
circuits.
Current consumption 24 V DC
600 mA
48 V DC
420 mA
115 V AC 280 mA
230 V AC 115 mA
* Sound 1
Operational
parameters
±10%
Line monitoring
Yes
Ambient conditions
Functional ambient
temperature range
24 V DC / 48 V DC: -50 to +XX* °C
115 V AC: -40 to +XX* °C
230 V AC: -40 to +XX* °C
XX* max. ambient temperature see certificate
Mechanical data
Degree of protection IP66 / IP67 (IEC/EN 60529)
Material
Enclosure
Glass fibre reinforced polyester
Horn and trumpet ABS, flame retardant
Lens cover
Polycarbonate
Protective grid
Stainless steel
Assembly parts
Stainless steel
Bracket
Stainless steel
Labels
Polyester foil, self-adhesive