Form No. 003-2282 Rev G
18
f.
For 208Vac system (1 branch of 208V at full rated kVA)
Jumper L22-N21
L23-N22 208V
N22
L22
N21
L23
L21
208V
NOTE:
For models with an isolation transformer, the output is configurable to
100V, 110V, and 115V systems by choice of inverter output settings (section
3.5.1.23) and internal connection of isolation transformer. Consult the factory if
voltage other than 120V, 208V, or 240V is necessary.
Use Mounting Cable Tie to attach cables.
4. Power connections must be made using the following tables for the input
current, output current and recommended conductors:
a. AC input and output
*- Maximum current shown is the rating of the recommended conductor
Model
*Maximum Current
Conductor Size
6KVA
33A
AWG #9
8KVA
54.3A
AWG #7
10KVA
54.3A
AWG #7
External Battery
External Charger
T1