SST-PFB-SLC User’s Guide
50
The program uses 80 ms and 160 ms internal timers to implement four states,
with a combined period of 320 ms. The OSR instructions ensure that the SLC
executes the COP instruction only at the start of one of these states. The result
is that all four blocks are accessed within the 320 ms combined period of the
two timers.
6.6
Example: Using Flex I/O
When you configure the Flex I/O using COM PROFIBUS, always configure
18 slots, even if the slots are empty. The first two slots are used for status,
with the first slot configured as an input word and the second slot as an output
word. The remaining 16 slots are used for I/O modules. For each module,
configure two slots.
Summary of Contents for SST-PFB-SLC
Page 7: ...Contents vii Technical Data 105 Index 107 A...
Page 8: ...SST PFB SLC User s Guide viii...
Page 14: ...SST PFB SLC User s Guide 6...
Page 20: ...SST PFB SLC User s Guide 12...
Page 34: ...SST PFB SLC User s Guide 26...
Page 53: ...45 6 DP Master Application Examples...
Page 56: ...SST PFB SLC User s Guide 48 Sample Program...
Page 57: ...DP Master Application Examples 49 Sample continued...
Page 66: ...Using the Scanner Module as a DP Slave 58...
Page 67: ...59 8 Using FDL...
Page 75: ...Using FDL 67 Sample Program...
Page 76: ...SST PFB SLC User s Guide 68 Sample Continued...
Page 80: ...SST PFB SLC User s Guide 72 Sample Program...
Page 81: ...SST PFB SLC User s Guide 73 Sample Continued...
Page 85: ...SST PFB SLC User s Guide 77...
Page 86: ...SST PFB SLC User s Guide 78...
Page 87: ...79 9 Diagnostics This chapter describes system diagnostics...
Page 105: ...97 11 Network Parameter Defaults This chapter describes network defaults...