2 Product Overview
2.1 Product Function
It can monitor data on the CAN network through Modbus TCP, TCP Server, TCP Client and UDP protocols,
etc.
2.2 Technical Specifications
2.2.1 Modbus TCP/CAN
[1]
Ethernet Side
Two 10M / 100M adaptive Ethernet port, half-duplex, full-duplex;
Support Modbus TCP protocol, as slaves (Modbus TCP server);
Support 03, 04, 16 function codes;
Input register start address is 0, support 04 function code;
Output register start address is 0, support 03, 16 function codes;
Each 8 registers (16 bytes) constitute 1 CAN frame;
Each Modbus TCP command packet contains up to 15 CAN frame;
Send buffer can cache up to 300 CAN frame (in the non-periodic transmission mode) and 50 CAN
frames (in the periodic transmission mode);
Receive buffer can cache up to 150 frame;
Support DHCP;
[2]
CAN Side
Support CAN2.0A and CAN2.0B;
CAN Baud rate support 1M, 500K, 250K, 125K, 100K, 50K, 20K, 10Kbps;
2.2.2 TCP Server/CAN
[1]
Ethernet Side
Two 10M / 100M adaptive Ethernet port, half-duplex, full-duplex;
Support TCP protocol, as server;
Support 4 Client connections;
Support forwarding CAN frame data to 4 TCP client and forward CAN frame data from 4 Client;
Gateway can cache up to 200 CAN frame data from TCP Client;
Supports static IP address configuration (manual allocation) and DHCP automatically assigns IP address;