User Manual
3-channel HART/Modbus TCP Gateway
GT200-3HT-MT
WWW.SSTCOMM.COM
13
(Power off then Power on)
3.3.2 Internal / External Sampling resistor Switch
GT200-3HT-MT can choose using the internal sampling resistor or external sampling resistor to get the
HART signal. The specification of the internal resistor is 270Ω, 2W. When the power of the sampling resistor
exceeds 2W, you must use the external resistor.
Switch to ON, using the internal
sampling resistor
Switch to OFF, using the external
sampling resistor
3.4 Interface
3.4.1 Power Interface
GND
NC
24V+
1
2
3
Pin
Function
1
Power GND
2
NC(Not Connected)
3
24V+, DC Positive 24V