4.2.2.4 Configure Slave Commands
Click the command number in the tree view; you will see the configuration plate in the right place:
Mode of outputting command: You can use the execution way of the command, change-of-state, polling output,
Initialization output and disable output optional;
Change-of-state output: Execute this command once s data buffer of HART changes
Polling output: This order is put in the polling list, executed periodically
Initialization output: Execute the command only once when power is on
Disable output: the command will not be sent.
Set starting address of sending data: 3000~4999;
The register starting address of sending data: the property is automatically calculated by gateway, used for register
addressing;
Sending data length (BYTE): used to set the length of output data by this command;
Sending data length (WORD): the property is automatically calculated by gateway, used for user checking output
data length, 1 word=2 byte;
Memory starting address of receiving data: set the memory address of input data by this command. Response data
only includes data area of HART frame;
The register starting address of receiving data: the property is automatically calculated by gateway, used for
register addressing;
Receiving data length (BYTE): set the length of input data by this command;
Receiving data length (WORD): the property is automatically calculated by gateway, used for user checking