Spring Air Systems Truflow-TC Installation and Operating May 2021
28
58
Press
SETTINGS
button
59
Press
FLA VALUES
button
60
Touch
MAX AIR
button on main screen. Status bar should increase and change to
RED
.
61
Press
SETTINGS
.
62
Press
FLA VALUES
and enter
MAX amps
value plus 2.0 amps for Kitchen 1
A
SETTING MAXIMUM and MINIMUM AMPS LOAD POINT - Kitchen 2 Exhaust
Item Description
Y / N
63
Make sure “
Kitchen 2
” is displaying above the status bar. Press
Kitchens
button to
alternate between kitchens. Press
SYSTEM ON
button. Allow 1 minute for systems to
stabilize.
64
Press
FAN STATUS
65
Touch
Max Hz
and set to 0.1 Hz higher than
Minimum
setting.
66
Record actual running Minimum Amps
A
67
Touch
Min FLA
and set to 2.0 Amps lower than value in Step 64. Return to
MAIN
screen.
A
68
Re-set
Max Hz
to value from Step 49
69
Press
SETTINGS
button
70
Press
FLA VALUES
button
71
Touch
MAX AIR
button on
MAIN
screen. Status bar should increase and change to
RED
.
72
Press
SETTINGS
.
73
Press
FLA VALUES
and enter
MAX amps
value plus 2.0 amps for Kitchen 2
A
SETTING MAX AIR DURATION TIMER
Item Description
Y / N
74
From
MAIN
screen, touch
SETTINGS
button.
75
Touch
K1
or
K2
MAX AIR
button.
76
Touch the box with the number in it. Change to 60. This will keep the Kitchen 1 or 2
exhaust and supply fans running at maximum speed for 60 minutes.
77
Take airflow readings for both exhaust and supply as indicated in the Hood start up report
portion of this start up.
78
If the hood airflows are higher or lower than the design, press
FAN STATUS
and increase
or decrease
Max Hz
by 2 Hz to raise or lower the fan speed.
79
Enter final
MAX Hz
value for Kitchen 1 Exhaust fan here.
Hz
80
Enter final
MAX Hz
value for Kitchen 2 Exhaust fan here.
Hz
81
If the max FLA of the motor has been reached and airflows
remain low, call
Spring Air Systems Service for further instructions.
1-866-874-4504 or 1-905-338-2999 ext 28
82
Reset the
K1
and
K2 MAX AIR
back to 20 minutes when airflow readings are completed.
ALL FANS SHOULD BE RUNNING AT LOW SPEED BEFORE YOU PROCEED TO TEST THE
J-COUPLE MODULATION OPERATION.
Item Description
Y / N
83
Check J-couple wires from
Kitchen 1
hoods are connected and the
End of Line
plug is
installed on the last J-couple.
84
Plug the
Kitchen 1
J-couple plug into the RPD panel in the
K1
receptacle. From the main
screen, touch the
SETTINGS
button. Log in if necessary. Touch the
NODE SETTINGS
button.
85
If
NODE
box is reading 0, Touch the number button beside
SET POINT
and lower the
set point to
55
.
86
The
SET POINT
value should be at or lower than ambient temperature.
87
Turn on cooking equipment. The
NODE
value should increase with temperature. The
OUTPUT
value will also increase. This will cause the corresponding Exhaust and Supply
VFD’s to speed up.
88
Turn off cooking equipment. VFDs should slow down as cooking equipment cools off.