IM-P323-25 CH Issue 3
50
Description
Features
(at 25°C environmental temp.)
OP1 output
OP2 output
OP3 output
AL2 - AL3 alarms
Setpoint
Tuning
OP4 countinuous control
output (option)
Galvanic isolation: 500 V~/1 min
Resolution 12bit (0.025%)
Accuracy: 0.1 %
In current: 0/4…20mA 750½/15V max
SPST Relay N.O., 2A/250V~ for resistive load
Triac, 1A/250V~ for resistive load
Logic not isolated: 5V–, ± 10%, 30mA max
SPST Relay N.O., 2A/250V~ for resistive load
Jumper selectable
(page 13)
SPST Relay N.O., 2A/250V~ for resistive load
Triac, 1A/250V~ for resistive load
Protection by
varistor
for 220V ~
and capacitor
Adaptive Tuning self-learning, not intrusive, analysis of the process response to perturbations and
continuously calculation of the PID parameters
Fuzzy-Tuning The controller selects automatically the best
method according to the process conditions
High limit
Hysteresis 0.1…10.0% c.s.
Action
Active high
Active low
Action type
Deviation threshold
±range
Band threshold
0…range
Absolute threshold
whole range
Sensor break, heater break alarm,
Latching/Blocking, Loop Break Alarm
from low range to high limit
from low limit to high range
Step response
Natural frequency
Low limit
Ramp up and down. User inhibited.
0.1…999.9 digit / min
Standard with bumpless function
+18V- ±20%, 30mA max. for external tranmitter supply
Auto/Man station
Auxillary supply