IM-P323-25 CH Issue 3
14
The functionality associated to each of the outputs is defined during the
configuration of the instrument, index L (see section 4.1).
The suggested combinations are:
3.3.5 Output configuration
Note: With heat or cool control AL2 and AL3 share the same output.
Output
Alarms
Primary
Secondary
AL2
AL3
A
Single Action
Heat or Cool
OP4
none
none
OP2
OP3
B
Single Action
Heat or Cool
OP4
none
none
OP1
OP3
C
Double Action
Heat
OP4
Cool
OP3
OP2
-
D
Double Action
Heat
OP4
Cool
OP2
-
OP3
E
Double Action
Heat
OP1
Cool
OP4
OP2
OP3
F
Double Action
Heat
OP2
Cool
OP4
OP1
OP3
G
Valve Motor Drive
Open
OP1
Close
OP3
OP2
OP2
H
Single Action
Heat or Cool
OP1
none
none
OP2
OP3
I
Single Action
Heat or Cool
OP2
none
none
OP1
OP3
J
Double Action
Heat
OP1
Cool
OP3
OP2
-
K
Double Action
Heat
OP1
Cool
OP2
-
OP3
L
Double Action
Heat
OP2
Cool
OP3
OP1
-
SX25 mA
SX25 VMD
Relay output
Relay output
Logic output
OP1 - OP3
OP2 - R
OP2 - L
OP2 output can be Relay or logic.
The 'jumper' on the auxiliary
board selects the output type:
Link Pins 1-2 for OP2-Relay
(Factory set)
Link Pins 2-3 for OP2-Logic
Auxiliary
board
Jumper