IM-P157-38
CMGT Issue 4
4
Steam/Water Mixing Stations (MkII valves - 2002 onwards) Safety and Operation
1.4 Warning
This product must only be installed and commissioned by qualified personnel
(see Section 1.5).
The hosedown station includes a safety device called the TCO1. This temperature cut-out valve
activates at a temperature of 95 °C (203 °F) to limit the discharge of steam in the event of a system
fault. This assumes 20 m (65.6 ft) hose installed - shorter length hoses may result in a brief discharge
of steam following activation of the TCO1.
The mixing valve must always be operated with an element in the TCO1 to prevent steam reaching
the hose. In the event that the hosedown station is used without an element in the TCO1 then
Spirax Sarco will not accept any consequential liability for the operation of the hosedown station
in this manner.
Always operate the hosedown station as instructed on the warning notice sent out with the
equipment; particularly regarding protective clothing. The WARNING NOTICE must always be
displayed by the mixing valve.
1.5 Qualified personnel
For the purposes of these operating instructions qualified personnel are persons who are
experienced in the installation, commissioning and operation of this product and who are suitably
qualified to perform their duties, e.g.:
-
Have received training or instruction in the maintenance and use of appropriate safety equipment
according to current safety standards.
-
Have received training in first-aid.
1.6 Safety test procedure
A safety check undertaken by qualified personnel must be carried out each time the unit is used.
The safety test and subsequent maintenance procedure ensures that live steam cannot be
discharged from the gun, which would happen in the event of e.g. a seized piston.
Due to the possible presence of steam, please ensure due care and attention are observed when
undertaking this task. Wear protective clothing, especially heavy duty gloves and safety glasses.
With the cold water inlet valve shut and the steam inlet valve open, carefully operate the gun. Before
pulling the trigger, hold the gun firmly in both hands and adopt a body position which will prevent
loss of balance due to recoil from the hose gun.
There should be no flow observed at the gun. If steam flow is detected during the test, or the
TCO1 activates, the hosedown station, it must be taken out of service immediately. Please refer
to Section 5, 'Maintenance'.