![Spirax Sarco MkII Safety And Operation Download Page 35](http://html.mh-extra.com/html/spirax-sarco/mkii/mkii_safety-and-operation_1347941035.webp)
IM-P157-38
CMGT Issue 4
35
Steam/Water Mixing Stations (MkII valves - 2002 onwards) Safety and Operation
Fig. 26
Hot water
outlet of the
mixing valve
'T' piece
Reducing nipple
Thermometer
OUTLET
TCO1
INLET
Reducing nipple
5.9 TCO1 Retro-fit pack
Please read in conjunction with Figure 26:
The TCO1 temperature cut-out valve can be retro-fitted to Spirax Sarco steam/water mixing valves that do
not already have them fitted.
This is strongly recommended.
The practice of retro-fitting a TCO1 will only
apply to some older installations where a TCO1 was not supplied with the original valve. This does not apply
to the valve design that is shown throughout this IMI. The procedure outlined below is therefore for the old
type of valve. There is only one size of TCO1 (1" nominal bore) which is suitable for both
½
" and
¾
" steam/
water mixing valves.
Installation:
1.
Isolate the steam and cold water supplies by closing the two ball valves.
2.
Discharge the contents of the hose and station by pulling the gun trigger and eliminate pressure until
the water flow stops.
3.
Remove the hose by splitting the union and unscrew the thermometer 'T' from the mixing valve hot water
inlet. Remove the nipple from the valve end of the 'T' piece.
4.
Assemble the TCO1 retro-fit pack; Screw the 1" x
½
" reducing nipple into the TCO1 marked 'INLET' for
the
½
" mixing valve, (for the
¾
" mixing valve it is a 1" x
¾
" reducing nipple). Screw the 1" x
¾
" reducing
nipple into the TCO1 marked 'OUTLET', (this is the same for both the
½
" and
¾
" mixing valves.)
5.
Attach the thermometer 'T' piece to the TCO1 retro-fit pack.
6.
Screw the TCO1 retro-fit pack into the hot water outlet of the mixing valve using PTFE tape or suitable
thread sealant. Care should be taken to ensure that the hexagon cap is in line with the dial face of the
thermometer when the arrangement is tightened into the valve.
7.
Attach the hose to the thermometer 'T' piece using the union.
IMPORTANT NOTE:
The TCO1 must be installed with the end
marked 'INLET' connected to the mixing
valve and the end marked 'OUTLET' to the
'T' piece. (These markings are stamped onto
the hexagon end connections). The TCO1 is
a safety device, if it is installed in reverse it
will never be able to operate.
Retro-fit
pack