Spirax Sarco LC2300 Installation And Maintenance Instructions Manual Download Page 5

IM-P402-72  AB Issue 6

5

3. Installation

WARNING
Isolate the mains supply before unplugging the controller since hazardous voltages
will be exposed on the controller base.
The controller must be installed in a suitable industrial control panel or fireproof enclosure to
provide impact and environmental protection (pollution degree 2). Spirax Sarco can provide
suitable plastic or metal enclosures (for the standard controller only).
To unplug the controller from its base, undo the two clamping screws and pull the controller
straight forwards. Rocking the controller in the vertical plane will ease removal.
The controller may be mounted on a 'top hat' DIN rail using the mounting clip provided, or the
clip may be removed and the controller base screwed directly to a chassis plate.
Caution: Allow 15 mm (

5

/

8

") spacing between multiple units for air circulation.

The controller is for installation category II (Overvoltage category) and must be installed in
accordance with IEC 60364 or equivalent. For the US and Canadian markets the controller
must be wired in accordance with the National and Local Electrical Code (NEC) or Canadian
Electrical Code (CEC). The controller and all connected circuits must have a common isolation
system which meets the relevant requirements of IEC 60947-1 and  IEC 60947-3 or equivalent.
This must be positioned close to the controller and clearly identified as the disconnect device.
A quick blow 3 amp external fuse must be fitted in all phases of the controller  supply.
Screened high temperature, 3 core, 1 mm

2

  (18 - 16 AWG) copper cable is required for the

probe wiring. The maximum permitted length is 100 metres (328 ft). Use cable with a suitable
temperature rating for the installation. Pirelli FP200 or Delta Crompton Firetuf OHLS are
suitable cables for the standard version. Use NEC Class 1 wiring for UL version.
Connect the screens as shown in the wiring diagrams (Section 5).
Cabling should be installed in accordance with BS 6739 - Instrumentation in Process Control
Systems: Installation design and practice or local equivalent.
If the product is not used in the manner specified in this IMI, then the protection
provided may be impared.

Archive

Summary of Contents for LC2300

Page 1: ...e Instructions IM P402 72 AB Issue 6 4025350 6 1 General safety information 2 General product information 3 Installation 4 Setting up the controller 5 Wiring diagrams 6 Commissioning 7 Maintenance 8 F...

Page 2: ...em An independent high water alarm system must be fitted if it is considered a safety requirement In this case the relays must simultaneously isolate the feedwater supply and the boiler heat supply at...

Page 3: ...ut current is greater than 50 i e above the set point output current The amber LED 100 0 Indicates that the output is greater than 20 mA or less than 0 4 mA A three stage wave filter gives an averaged...

Page 4: ...ntain the integrity of the approval Maximum power consumption 6 VA 0 2 V Input 1 0 6 V Selectable inputs 0 20 mA 4 20 mA Input 2 opposite sense to input 1 0 20 mA 4 20 mA Note See separate literature...

Page 5: ...nt For the US and Canadian markets the controller must be wired in accordance with the National and Local Electrical Code NEC or Canadian Electrical Code CEC The controller and all connected circuits...

Page 6: ...switches to the positions shown in Figure 3 for the chosen functions Replace the printed circuit board Ensure that the LEDs engage with the holes in the front panel Replace the rear cover panel Note t...

Page 7: ...aves and high turbulence may otherwise cause continuous oscillation of the output signal giving over frequent valve movement The unit is supplied set to Filter 1 position the least damped response wit...

Page 8: ...earth A functional earth is used in order for the product to operate In this application the earth tank boiler shell is used as the common of the probe preamplifier It also provides a sink drain for a...

Page 9: ...rown Red Black LC2300 controller Screen Screen Fig 4 5 2 Wiring diagram standard version 4 20 mA Test Connect ammeter between Terminals 5 and 6 Do not disconnect loop This earth terminal is internally...

Page 10: ...ng to a 4 20 mA level transducer The controller can be connected to a self powered or loop powered 4 20 mA level transducer instead of a capacitance probe Connect wiring as shown in the Figures 6 and...

Page 11: ...are shown Wiring connections for other Spirax Sarco controllers transmitters are different and are given in the individual Installation and Maintenance Instructions Fig 8 Capacitance probe source Fig...

Page 12: ...g or maintenance of the controller is necessary Boiler water level controls and level alarms however do require testing and inspection General guidance is given in the UK Health and Safety Executive G...

Reviews: