background image

IM-P402-72  AB Issue 6

2

1. General safety information

Your attention is drawn to the  Safety Information leaflet, IM-GCM-10, as well as to any
National or local regulations.
Safe operation of the product depends on it being properly installed, commissioned
and maintained by a qualified person in compliance with the operating instructions.

It is essential to comply with  general installation and safety instructions for pipeline
and plant construction, as well as to make proper use of tools and safety equipment.
The product is designed and constructed to withstand the forces encountered
during normal use. Use of the product for any other purpose, or failure to install the
product in accordance with these Installation and Maintenance Instructions, could cause
damage to the product, will invalidate any        marking, and may cause injury or fatality
to personnel.

Additional Safety Notes:
Level control and level limiting products in steam boilers

Products / systems must be selected, installed, operated, and tested in accordance with:

-

Local or National standards and regulations.

-

Guidance Notes, (Health and Safety Executive PM5 in the UK).

-

The requirements of Approvals Authorities.

-

Boiler Inspection Bodies.

-

Boiler manufacturer’s specifications.

Two independent low water limiting systems must be installed on steam boilers.
Level probes must be installed in separate protection tubes / chambers, with
sufficient clearance between the tips, and earth.

Each probe must be connected to an independent controller. The alarm relays
must isolate the boiler heat supply at low alarm status.
A high water alarm may be part of the water level control, or a separate system. An
independent high water alarm system must be fitted if it is considered a safety requirement.
In this case, the relays must simultaneously isolate the feedwater supply and the boiler heat
supply at high alarm status.  All boiler water limiters require regular functional testing.
The level probe and controller is only part of the safety system. To complete the
system, additional circuitry (wiring, relays, alarm bell / lamp etc.) is required.  Circuitry
must be designed and wired to 'fail-safe'.

A suitable water treatment regime must be used to ensure continuous safe and correct
operation of the control and limiter systems. Consult the above authorities and a
competent water treatment company.

Warning

Isolate the mains supply before unplugging the controller since hazardous voltages will
be exposed on the controller base. This product complies with the requirements
of Electromagnetic Compatibility Directive 89 / 336 / EEC by meeting the standards of:

-

Emissions EN 61326: 1997 A1 + A2 Class B equipment Table 4.

-

Immunity

EN 61326: 1997 A1 + A2 Class A equipment Table 1.

The following conditions should be avoided as they may create interference above
the limits specified in EN 61326 (Immunity) if:

-

The product or its wiring is located near a radio transmitter.

-

Excessive electrical noise occurs on the mains supply. Power line protectors (ac)
should be installed if mains supply noise is likely. Protectors can combine filtering,
suppression, surge and spike arrestors.

-

Cellular telephones and mobile radios may cause interference if used within
approximately 1 metre (39") of the product or its wiring. The actual separation distance
necessary will vary according to the surroundings of the installation and the power
of the transmitter.

If this product is not used in the manner specified by this IMI, then the protection
provided may be impaired.

Archive

Summary of Contents for LC2300

Page 1: ...e Instructions IM P402 72 AB Issue 6 4025350 6 1 General safety information 2 General product information 3 Installation 4 Setting up the controller 5 Wiring diagrams 6 Commissioning 7 Maintenance 8 F...

Page 2: ...em An independent high water alarm system must be fitted if it is considered a safety requirement In this case the relays must simultaneously isolate the feedwater supply and the boiler heat supply at...

Page 3: ...ut current is greater than 50 i e above the set point output current The amber LED 100 0 Indicates that the output is greater than 20 mA or less than 0 4 mA A three stage wave filter gives an averaged...

Page 4: ...ntain the integrity of the approval Maximum power consumption 6 VA 0 2 V Input 1 0 6 V Selectable inputs 0 20 mA 4 20 mA Input 2 opposite sense to input 1 0 20 mA 4 20 mA Note See separate literature...

Page 5: ...nt For the US and Canadian markets the controller must be wired in accordance with the National and Local Electrical Code NEC or Canadian Electrical Code CEC The controller and all connected circuits...

Page 6: ...switches to the positions shown in Figure 3 for the chosen functions Replace the printed circuit board Ensure that the LEDs engage with the holes in the front panel Replace the rear cover panel Note t...

Page 7: ...aves and high turbulence may otherwise cause continuous oscillation of the output signal giving over frequent valve movement The unit is supplied set to Filter 1 position the least damped response wit...

Page 8: ...earth A functional earth is used in order for the product to operate In this application the earth tank boiler shell is used as the common of the probe preamplifier It also provides a sink drain for a...

Page 9: ...rown Red Black LC2300 controller Screen Screen Fig 4 5 2 Wiring diagram standard version 4 20 mA Test Connect ammeter between Terminals 5 and 6 Do not disconnect loop This earth terminal is internally...

Page 10: ...ng to a 4 20 mA level transducer The controller can be connected to a self powered or loop powered 4 20 mA level transducer instead of a capacitance probe Connect wiring as shown in the Figures 6 and...

Page 11: ...are shown Wiring connections for other Spirax Sarco controllers transmitters are different and are given in the individual Installation and Maintenance Instructions Fig 8 Capacitance probe source Fig...

Page 12: ...g or maintenance of the controller is necessary Boiler water level controls and level alarms however do require testing and inspection General guidance is given in the UK Health and Safety Executive G...

Reviews: