IM-P681-07
CMGT Issue 2
13
Fig. 3
Fig. 2 Customer connections
L1
L2
L3
N
E
60
61
66
67
68
Supply
380 - 415 v
3 phase 50 Hz
4 wire
Common motor
wire fault alarm
Opens on alarm
High level alarm
Opens on alarm
3.4 Pump motor rating and overload settings.
Pump
Pump Kw
50Hz
Overload
Overload
setting
Control panel material
Carbon steel
Stainless steel
CM3-3 and CM3-4
0.46
1.0 - 1.6A
1.1A
173
177
CM10-1
0.6
1.4 - 2.0A
1.9A
174
178
CM10-2
1.2
2.5 - 4.0A
2.9A
175
179
CM10-3
2.2
4.0 - 6.0A
4.6A
176
180
CM15-1
1.2
2.5 - 4.0A
2.9A
175
179
CM15-2
2.2
4.0 - 6.0A
4.6A
176
180
3.5 Lifting
The CRU 200 and 500 units should be lifted by a
suitable forklift truck from underneath the frame,
placed in position and securely bolted to the floor.
Warning:
On no account is the CRU to be lifted by any other
part other than the frame (see Figure 3).
Note:
Sufficient space should be provided around
the unit location to allow access for maintenance.
3.3 CRU 200 and 500 series wiring
See inside of control panel door for specific wiring diagram.