IM-P358-26
CH Issue 1
17
3.6.1 Valve motor drive models
Fig. 14 Actuator termination PCB
(
Note:
PE protective earth connection is on housing plate).
Table 2 Fuse ratings for all variants of the AEL5_ _ _ _ actuators
X10
X5
X9
X4
X6
PE
X11
X0
X1
X7
X2
X3
1
6
7
4
2
1
2
X1
= Internal wiring
X2
= Internal wiring
X3
= Internal wiring
X4
= Potentiometer 1
(optional)
X5/1 = Neutral
X5/2 = Motor phase to open
X5/4 = Motor phase to close
X6
= Additional position
switch (optional)
X7
= not used
X9
= Potentiometer 2
(optional)
X0
= Potentiometer 2
(optional)
PE
= Earth connection
to housing
X10 = Not used
Actuator
Power supply / frequency Fuse
(A)
Actuator
Power supply / frequency Fuse
(A)
AEL51211
230 V
50 / 60 Hz
0.125
AEL54211
230 V
50 / 60 Hz
0.63
AEL51212
115 V
50 / 60 Hz
0.25
AEL54212
115 V
50 / 60 Hz
1.25
AEL51213
24 V
50 / 60 Hz
1
AEL54213
24 V
50 / 60 Hz
3.15
AEL51214
24 V
Continuous
1.6
AEL54214
24 V
Continuous
1.6
AEL52211
230 V
50 / 60 Hz
0.16
AEL55311
230 V
50 / 60 Hz
0.63
AEL52212
115 V
50 / 60 Hz
0.315
AEL55312
115 V
50 / 60 Hz
1.25
AEL52213
24 V
50 / 60 Hz
1.6
AEL55313
24 V
50 / 60 Hz
3.15
AEL52214
24 V
Continuous
1
AEL55314
24 V
Continuous
4
AEL53211
230 V
50 / 60 Hz
0.25
AEL53211
230 V
50 / 60 Hz
0.8
AEL53212
115 V
50 / 60 Hz
0.5
AEL53212
115 V
50 / 60 Hz
1.6
AEL53213
24 V
50 / 60 Hz
1.6
AEL53213
24 V
50 / 60 Hz
6.3
AEL53214
24 V
Continuous
1.6
Summary of Contents for AEL5 Series