4-28
Chapter 4: OE2CIH and HART
User’s Manual Pub. 0300272-03 Rev. B
Table 4-20 Suspend Normal HART Acquisitions (Service Code = 0×51)
Unconnected Message
Field
Value
Definition
Message Type
CIP Generic
Service Code
0×51
Suspend HART
Class Name
0×035D
HART Object
Instance
0 = All Channels
1 to
n
= Single Channel(
n-1
)
All channels
suspended or a
single channel
Object Attribute
None, leave this field blank
Request Size
0
No Request Data
Reply Size
2
Number of Data
bytes returned
Request Data
Suspend Normal HART acquisitions - Request packet structure
Request Size = 0
Offset Field
Value
Definition
No Request Data
Reply Data
Suspend Normal HART acquisitions - Reply packet structure
Reply Size = 2 bytes
Offset Field
Value
Definition
0
Status
(1 byte)
00 = SUCCESS
35 = DR_DEAD
1
Pad
0
Table 4-21 Resume Normal HART Acquisitions (Service Code = 0×52)
Unconnected Message
Field
Value
Definition
Message Type
CIP Generic
Service Code
0×52
Resume HART
Class Name
0×035D
HART Object
Instance
0 = All Channels
1 to
n
= Single Channel (
n-1
)
All channels resume
or a single channel
Object Attribute
None, leave this field blank
Request Size
0
No Request Data
Reply Size
2
Number of Data
bytes returned
Summary of Contents for 1734
Page 1: ......
Page 6: ...vi Point IO 2 Channel Isolated Output Analog HART Module User s Manual Pub 0300272 03 Rev B ...
Page 10: ...1 4 Chapter 1 Module Overview User s Manual Pub 0300272 03 Rev B ...
Page 13: ...Chapter 1 Module Overview 1 7 User s Manual Pub 0300272 03 Rev B See the block diagram below ...
Page 14: ...1 8 Chapter 1 Module Overview User s Manual Pub 0300272 03 Rev B ...
Page 24: ...2 10 Chapter 2 Installation and Wiring User s Manual Pub 0300272 03 Rev B ...
Page 36: ...3 12 Chapter 3 Configuring the Module User s Manual Pub 0300272 03 Rev B ...
Page 68: ...4 32 Chapter 4 OE2CIH and HART User s Manual Pub 0300272 03 Rev B ...
Page 74: ...A 6 Appendix A Module Specifications User s Manual Pub 0300272 03 Rev B ...
Page 76: ...I 2 Index User s Manual Pub 0300272 03 Rev B ...