Chapter 1: Module Overview
1-7
User’s Manual Pub. 0300322-01 Rev. B
Environmental Tests
Test Limits
Shock (Operating)
(Performance Criteria A)
25 G, 11 ms half-sine (3 mutually perpendicular axes)
Shock (Non-operating)
(Performance Criteria B)
25 G (35 G Panel mount), 11 ms half-sine (3 mutually
perpendicular axes)
Radiated Emissions
(Enclosure) Class A, 30 MHz – 1 GHz
Conducted Emissions
Group 1, Class A (AC Mains), 150 kHz – 30 MHz
ESD immunity
(Performance Criteria B)
6 kV Indirect (Coupling Plate)
6 kV Contact Discharge (to points of initial contact)
8 kV Air Discharge (to points of initial contact)
Radiated RF immunity
(Performance Criteria A)
10 V/M with 200 Hz square-wave 50% Pulse 100% AM at 900
& at 1890 MHz
10 V/M with 1 kHz sine-wave 80% AM from 80…2000 MHz
3 V/M with 1 kHz sine-wave 80% AM from 2000…6000
MHz (10 V/M goal)
EFT/B immunity
(Performance Criteria B)
Signal Ports:
±2 kV at 5 kHz for 5 minutes, Criteria B
Power Ports:
±2 kV at 5 kHz for 5 minutes, Criteria B
Surge transient immunity
(Performance Criteria B)
Signal Ports:
±2 kV line-earth {CM} at 2
Ω on shielded ports
Power Ports
±2 kV CM at 12 Ω
±1 kV DM at 2 Ω
Conducted RF immunity
(Performance Criteria A)
10 VRMS with 1 kHz sine wave 80% AM from 150 kHz…80
MHz on signal and power ports
Magnetic Field
(Performance Criteria A)
30 Arms/m
AC Mains Voltage Dips, Interruptions
and Variations
Follow the 61000-4-11.
Table 1-4. Safety Test Specification Table
Safety Tests
Industry Standards
UL Safety
UL 61010-2-201 Safety Requirements for Electrical Equipment for
Measurement, Control, and Laboratory Use - Part 2-201: Particular
Requirements for Control Equipment (NRAQ, NRAQ7)
CAN/CSA C22.2 No. 61010-1-12 (Safety Requirements for Electrical
Equipment for Measurement, Control,
and Laboratory Use – Part 1: General Requirements)