Micro800™ 4 Ch Universal Analog Input Module
11
Publication 0100189-04 Rev. C
Adding the IF4U to CCW
The 2080sc-IF4U is configured for CCW (Connected Components
Workbench) using the PLUGIN_READ and PLUGIN_WRITE instructions
for generic plug-in modules.
The configuration, input data, and status structures discussed in the
sections above, are stored at different memory locations in the module.
The following table lists the memory location offset for each parameter
which is used when configuring the PLUGIN_READ, WRITE, and INFO
instructions.
Table 7 (Parameter Offset)
Parameter
Offset
(Dec)
Comments
MOD_ID_LO
0
Module ID
MOD_ID_HI
1
VENDOR_ID_LO
2
Vendor ID
VENDOR_ID_HI
3
PRODUCT_TYPE_LO
4
PRODUCT_TYPE_HI
5
PRODUCT_CODE_LO
6
PRODUCT_CODE_HI
7
MOD_REV_LO
8
Minor revision, 1-255
MOD_REV_HI
9
Major revision, 1-127
MOD_STATUS
16
Module status register
(see Table 6)
SYNC_DATA_LATCH
26
Writing 0xA5 to this register triggers input data latch
CONFIG_IN0_LO
32
Channel Configuration
Registers
CONFIG_IN0_HI
33
CONFIG_IN1_LO
34
CONFIG_IN1_HI
35
CONFIG_IN2_LO
36
CONFIG_IN2_HI
37
CONFIG_IN3_LO
38
CONFIG_IN3_HI
39
INPUT_DATA_0_LO
48
Input Data
(Format is 16-bit signed integer)
INPUT_DATA_0_HI
49
INPUT_DATA_1_LO
50
INPUT_DATA_1_HI
51
INPUT_DATA_2_LO
52
INPUT_DATA_2_HI
53
INPUT_DATA_3_LO
54
INPUT_DATA_3_HI
55
CJC_DATA_LO
56
CJC_DATA_HI
57
OC_STATUS
80
Open-circuit status
U_O_RANGE_STATUS
81
Under/over range status