Installation
16 EN
06|2019
4.4 Electrical
connection
WARNING
Risk of electric shock due to incorrect connections!
Electrical
connections
must always be carried out by
authorised specialists.
Observe
VDE
and
utility company regulations.
Install
a
disconnecting device with at least a 3 mm contact
gap per pole to interrupt the power supply.
Protect power supply with a ground fault circuit interrupter,
nominal residual current I
FN
≤
30 mA.
Only use suitable pipe types according to regional
regulations.
Adjust minimum diameter of the electrical pipes to
accommodate the motor output and pipe length.
If hazardous situations can occur, provide an emergency off
switch according to DIN EN 809. The builder/operator must
make a decision according to this standard.
Fig. 4