SPECIFICATION SUGGESTIONS

1.01

ZONE CONTROL SYSTEMS

A.

l. Provide a SC-Z20 zone control system manufactured by Specified Controls

Genera
to meet the performance as specified in this section. Each zone control system shall
meet the following requirements.

1.

The zone control system shall be composed of one logic panel, up to 20 zone
dampers with actuators, zone thermostats, and bypass damper(s).

2.

The zone control system shall be capable of controlling up to 20 zones and
must use proprietary fully modulating thermostats.

3.

The system shall have auto changeover and be capable of controlling two
stages of heat and two stages of cooling. The system shall also be
compatible with heat pump systems.

4.

The zone control system shall

require any field programming. A

not

laptop computer or service tool shall

be required for setup and

not

troubleshooting.

B.

. The zone control panel shall be suitable for the indoor ambient

Environment
conditions and shall be rated for operation between 32°F and 120° F.

C.

. Provide diagnostic LEDs for heating stages, cooling stages, fan,

Serviceability
and the heating or cooling request of each zone.

D.

. The zone control system shall

require a battery back-up.

No battery back-up

not

E.

. The zone control system shall be able to operate

Power and Immunity to noise
between 90% and 110% of nominal voltage rating and shall not be affected by
radio frequency interference (RFI).

1.02

ZONE DAMPERS

A.

Zone dampers shall be round, rectangular or VAV diffuser type. Round dampers
shall have a diameter of 6 inch to 36 inch. Rectangular dampers shall have a
minimum size of 8 inch by 8 inch. VAV diffusers shall have an inlet size of
6 inch to 14 inch.

1.

. 18 gauge (minimum) galvanized steel.

Frames

2.

. 18 gauge (minimum) galvanized steel.

Blades

3.

. Oil impregnated sintered iron bushings.

Bearings

Summary of Contents for SC-Z20

Page 1: ...SC Z20 Commercial Zone Control System Modulating or Two position Installation Manual...

Page 2: ...Works with single stage multi stage or heat pump systems No programming required Auxiliary heat control option for each zone Night setback option All low voltage wiring LEDs indicates status of equipm...

Page 3: ...second stage The system will remain in whatever mode it is in for a minimum of fifteen minutes If equal heating and cooling calls take place cooling will receive priority Equipment mode of operation i...

Page 4: ...SC Z20 MODULATING ZONE CONTROL SYSTEM WIRING AND LAYOUT GUIDE 3 SC Z20 NS NIGHT STAT SC Z20...

Page 5: ...OOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT 4 AMP PC BOARD HP HC SYSTEM B O REV VALVE 3 ZONES OFF MINIMUM 2 ZONES OFF CALLS ON OFF ECONO SPEED UP MODE STATUS HEAT COOL DAS ACTIVE OCCUPI...

Page 6: ...on Zones 1 20 RED Heat ON when there is a call for heating GREEN Cool ON when there is a call for cooling HVAC System W1 GREEN ON when first stage heat is energized W2 GREEN ON when second stage heat...

Page 7: ...T COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT COOL HEAT 4 AMP PC BOARD HP HC SYSTEM B O REV VALVE 3 ZONES OFF MINIMUM 2 ZONES OFF CALLS ON OFF ECONO SPEED UP MODE TIME DELAYS DIVIDED BY 15 STATU...

Page 8: ...AT Insert a small flat bladed screw driver in the release slot located on the bottom of the thermostat and pry straight up and away from the subbase Avoid twisting the case as this may stress the LCD...

Page 9: ...rge air temperature at the damper is below 72 degrees the zone damper will open on a call for cooling SC Z20 PANEL NOTES Use standard 18 gauge thermostat wire Run four wire cable from the panel termin...

Page 10: ...S DS HEAT COOL WIRE TO OPTIONAL SLAVE DAMPER UP TO 20 MAY BE WIRED IN PARALLEL SC Z20 T AUTO CHANGEOVER SPACE THERMOSTAT FACTORY JUMPER RED LED INDICATES A CALL FOR HEATING GREEN LED INDICATES A CALL...

Page 11: ...t T terminals on the SC Z20 panel that places the system in the occupied or unoccupied mode of operation The thermostat can also be used with a SC T32 S1 Indoor Remote Sensor 24 volt power to the ther...

Page 12: ...HE CLOCK AND DAY OF WEEK It is important that the time of day and day of the week is set properly so that occupied and unoccupied programs start on time 1 Touch the until the day of the week flashes T...

Page 13: ...ram to additional days of the Program CPY week use the or arrow to add additional days Example UP DOWN Mon Tue Wed Thu Fri 13 Once you have selected the days to be copied touch will begin to flash and...

Page 14: ...hat the HVAC equipment have two stages of heating and two stages of cooling The pressure drop through the zone dampers is negligible and should not be a factor when sizing branch duct runs Zone damper...

Page 15: ...e from each zone damper Connect terminals and R C Y W R C Y W from each zone damper to the terminals labeled and on the interface board 18 4 thermostat wire is recommended SC Z20 NS PROGRAMMABLE NIGHT...

Page 16: ...discharge air setpoint If the number of zones calling for heating and cooling are equal the system will operate in the cooling mode first This is known as Cooling Priority Each zone damper or diffuse...

Page 17: ...ol shall be required for setup and not troubleshooting B The zone control panel shall be suitable for the indoor ambient Environment conditions and shall be rated for operation between 32 F and 120 F...

Page 18: ...nected to the output shaft 2 All actuators shall be factory wired to the damper control board 3 All damper actuators shall be mounted outside of the air stream B The damper actuator control board shal...

Page 19: ...ermostat wire 18 gauge minimum No shielded cable shall be required 3 Control wire and cable shall be installed in accordance with NEC 1 06 SERVICE AND GUARANTEE A The entire zone control system shall...

Reviews: